| Plan Review Notes For Permit 22081153 |
| Permit Number |
22081153 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-25 11:16:14 | | | | FINAL ELEVATION CERTIFICATE | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NUMBER OF PERMANENT FLOOD OPENINGS LISTED FOR | | | ITEM A8(A) IS (9). ITEM A8(D) SPECIFIES THE VENTS AS | | | BEING ENGINEERED. THE FLOOD VENT DETAIL ON THE | | | ARCHITECTURAL PLANS SPECIFY (14) SMART VENTS MODEL | | | NUMBER 1540-520, WHICH HAVE A CAPACITY OF 200 SQFT PER | | | VENT. THE CRAWL SPACE AREA IS 2771 SQFT. NINE (9) OF | | | THESE VENTS ARE ONLY GOOD FOR 9 X 200 = 1800 SQFT. | | | ADDITIONAL VENTS ARE REQUIRED. FBC-R322.2.2 | | | | | | 2) SINCE THIS BUILDING HAS NO ATTACHED GARAGE THE BOXES | | | FOR A9 (D) SHOULD NOT BE MARKED. | | | | | | 3) SPECIFY THE ENGINEERED FLOOD VENTS THAT WERE USED IN | | | THE COMMENTS. | | | | | | 4) PROVIDE PHOTOS THAT SHOW THE FLOOD VENTS ON AT LEAST | | | TWO OF THE ELEVATIONS. | | | | | | 5) THE PHOTOS NEED TO BE DATED. | | | | | | 6) THE PHOTOS NEED TO STATE ?FRONT VIEW? ?REAR VIEW? | | | ??RIGHT SIDE VIEW? ?LEFT SIDE VIEW? PER INSTRUCTIONS. | | | | | | 7) SECTION ?D? THE BOX ?CHECK HERE IF ATTACHMENTS? | | | SHOULD BE CHECKED (FOR THE FLOOD VENT ENGINEERING) ? | | | SEE FEMA ELEVATION INSTRUCTIONS ?ITEMS A8B-D? | | | | | | | | | |
|