Plan Review Notes
Plan Review Notes For Permit 22081153
Permit Number 22081153
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-25 11:16:14 
 FINAL ELEVATION CERTIFICATE
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NUMBER OF PERMANENT FLOOD OPENINGS LISTED FOR
 ITEM A8(A) IS (9). ITEM A8(D) SPECIFIES THE VENTS AS
 BEING ENGINEERED. THE FLOOD VENT DETAIL ON THE
 ARCHITECTURAL PLANS SPECIFY (14) SMART VENTS MODEL
 NUMBER 1540-520, WHICH HAVE A CAPACITY OF 200 SQFT PER
 VENT. THE CRAWL SPACE AREA IS 2771 SQFT. NINE (9) OF
 THESE VENTS ARE ONLY GOOD FOR 9 X 200 = 1800 SQFT.
 ADDITIONAL VENTS ARE REQUIRED. FBC-R322.2.2
  
 2) SINCE THIS BUILDING HAS NO ATTACHED GARAGE THE BOXES
 FOR A9 (D) SHOULD NOT BE MARKED.
  
 3) SPECIFY THE ENGINEERED FLOOD VENTS THAT WERE USED IN
 THE COMMENTS.
  
 4) PROVIDE PHOTOS THAT SHOW THE FLOOD VENTS ON AT LEAST
 TWO OF THE ELEVATIONS.
  
 5) THE PHOTOS NEED TO BE DATED.
  
 6) THE PHOTOS NEED TO STATE ?FRONT VIEW? ?REAR VIEW?
 ??RIGHT SIDE VIEW? ?LEFT SIDE VIEW? PER INSTRUCTIONS.
  
 7) SECTION ?D? THE BOX ?CHECK HERE IF ATTACHMENTS?
 SHOULD BE CHECKED (FOR THE FLOOD VENT ENGINEERING) ?
 SEE FEMA ELEVATION INSTRUCTIONS ?ITEMS A8B-D?
  
  
  