| Plan Review Notes For Permit 22081100 |
| Permit Number |
22081100 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-06 16:39:52 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC EB 702.5, REVISE PLAN TO SHOW WHAT TYPE OF | | | WINDOW IS BEING REPLACED. NOTE THAT THE WINDOWS MARKED | | | AS "EGRESS" DO NOT MEET EGRESS REQUIREMENTS. FOR | | | INSTANCE, OPENING 4 SHOWS A DIMENSIO OF 36.25X49.75 FOR | | | A HORIZONTAL ROLLER WINDOW. IF THIS IS THE OPENING SIZE | | | REVISE THE PLAN TO CLARIFY AND ALSO INCLUDE THE OVERALL | | | DIMENSION AS THAT IS WHAT IS USED TO DETERMINE DESIGN | | | PRESSURE REQUIREMENTS. | | | | | | 2. FBC R 703.4, SUBMIT A FLASHING DETAIL. | | | | | | | | | |
|