 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 PERMIT #22081081 BUILDING REVIEW FAILED. 411 SUMMA ST.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL30343.07-R2 IS NOT RATED FOR USE IN ZONE 2
 OR ZONE 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D
 HAVE EITHER FLAT ROOF OR GABLE/HIP ROOF WITH MAX SLOPE
 OF 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT