| 2022-10-13 11:04:18 | 1ST REVIEW FMC |
| | PERMIT: 22081027 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS AND THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON THE |
| | 2020 FLORIDA ENERGY CODE. |
| | |
| | 2) PLEASE ADD A NOTE ON THE REFRIGERATION DRAWINGS |
| | STATING THAT ALL REFRIGERATION WILL REQUIRE A SEPARATE |
| | PERMIT APPLICATION, SUBMITTAL AND REVIEW AS IT WILL NOT |
| | BE REVIEWED UNDER THIS PERMIT APPLICATION. THEY WILL |
| | ALSO BE REQUIRED TO MEET- FEC C403.2.14 REFRIGERATION |
| | EQUIPMENT PERFORMANCE. |
| | REFRIGERATION EQUIPMENT PERFORMANCE SHALL BE DETERMINED |
| | IN ACCORDANCE WITH SECTIONS C403.2.14.1 AND C403.2.14.2 |
| | FOR COMMERCIAL REFRIGERATORS, FREEZERS, |
| | REFRIGERATOR-FREEZERS, WALK-IN COOLERS, WALK-IN |
| | FREEZERS AND REFRIGERATION EQUIPMENT. THE ENERGY USE |
| | SHALL BE VERIFIED THROUGH CERTIFICATION UNDER AN |
| | APPROVED CERTIFICATION PROGRAM OR, WHERE |
| | A CERTIFICATION PROGRAM DOES NOT EXIST, THE ENERGY USE |
| | SHALL BE SUPPORTED BY DATA FURNISHED BY THE EQUIPMENT |
| | MANUFACTURER. |
| | EXCEPTION: |
| | WALK-IN COOLERS AND WALK-IN FREEZERS REGULATED UNDER |
| | FEDERAL LAW IN ACCORDANCE WITH SUBPART R OF 10 CFR 431. |
| | |
| | 3) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR |
| | ALL NEW MECHANICAL UNITS. FEC C403.2.1 |
| | |
| | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF |
| | SPACE FOR THIS PROJECT. PLEASE USE THE OCCUPANCY |
| | CLASSIFICATIONS LISTED IN TABLE 403.3.1.1 WHEN NAMING |
| | EACH SPACE. FMC 403.3.1.1 |
| | |
| | 5) SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS |
| | EXHAUST SYSTEM. FMC TABLE 403.3.1.1 |
| | |
| | |
| | 6) SHEET M311: THERE ARE 3 CU???S SHOWN ON THE DRAWING |
| | FOR AC-3, AC-4 AND AC-5. ARE THESE NEW CU???S GOING TO |
| | BE MOUNTED ON THE ROOF? IF SO PLEASE SHOW THE ANCHORAGE |
| | DETAILS. FBC 107.3.5 |
| | |
| | 7) PLEASE SHOW A MECHANICAL ROOF DRAWING SHOWING THE |
| | EXISTING AND NEW SYSTEMS AND THE DISTANCE FROM THE |
| | ROOFS EDGE. FMC 304.11 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |