| 2022-10-27 16:22:05 | TARGET REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING S001 AND THE STRUCTURAL CALCULATIONS |
| | PROVIDED SHOW A WIND SPEED OF 168MPH USED FOR THE WIND |
| | DESIGN - WIND SPEED FOR A RISK CATEGORY II SHOULD BE |
| | 170MPH PER FBC WPB SECTION 120. |
| | |
| | 2) DRAWING AD110 SHOWS THE REMOVAL OF 2 EXIT DOORS FOR |
| | EXIT NUMBER 4 - DRAWING A020 SHOWS THE DOORS REPLACED |
| | WITH A WALL - DRAWING A021 SAYS THAT THE EXIT CONSIST |
| | OF 1 - 8' EXIT AND 1 - 3' EXIT PLEASE RE EVALUATE THE |
| | MEANS OF EGRESS - FBC 1005.4 CONTINUITY. |
| | THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF |
| | EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT |
| | BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL |
| | ARRIVAL AT THE PUBLIC WAY. |
| | |
| | 3) DRAWING ACC2 SHOWS THE ACCESSIBLE PARKING SPACE |
| | WIDTH AT 11' - SHOULD BE 12' PER FBC 502.2 VEHICLE |
| | SPACES. |
| | EACH PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM) |
| | WIDE, |
| | |
| | 4) PLEASE PROVIDE A NOTE ON THE DRAWINGS AS TO THE WALL |
| | FINISH AND CEILING FINISH FIRE CLASSIFICATIONS PER FBC |
| | 803.1 |
| | |
| | 5) PLEASE SHOW THE REQUIREMENT FOR TERMITE TREATMENT |
| | FOR THE DISTURBED SOILS PER FBC 1816.1.2 |
| | |
| | 6) STRUCTURAL DRAWINGS SAY TO SEE THE ARCHITECTURAL |
| | DRAWINGS FOR THE EXTERIOR WALL FINISHES/CLADDING ETC. - |
| | I DO NOT SEE ANY EXTERIOR WALL DETAILS ON THE |
| | ARCHITECTURAL DRAWINGS - FBC 1403 |
| | |
| | 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT |
| | APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY |
| | THE BUILDING DESIGNER OF RECORD FBC WPB 107.3.4 |
| | |
| | 8) ACCESSIBLE RESTROOM - WHEN REFERRING TO THE MIRROR |
| | OVER THE SINK DIMENSIONS FROM THE FLOOR PLEASE USE THE |
| | WORD "REFLECTIVE SURFACE" FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 9) PLEASE PROVIDE A STATEMENT ON THE DRAWING THAT THE |
| | STORAGE RACKS COMPLY WITH RMI/ANSI MH 16.1 - FBC 2209.1 |
| | STORAGE RACKS. |
| | THE DESIGN, TESTING AND UTILIZATION OF STORAGE RACKS |
| | MADE OF COLD-FORMED OR HOT-ROLLED STEEL STRUCTURAL |
| | MEMBERS SHALL BE IN ACCORDANCE WITH RMI/ANSI MH 16.1. |
| | |
| | |