| 2022-09-15 06:13:56 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 2ND REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | | | | PERMIT #22081026 BUILDING REVIEW FAILED. 323 PUTNAM | | | RANCH RD. | | | 1. SUBMITTED MIAMI-DADE COUNTY NOA 20-0723.09 COVERS | | | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(24). | | | SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND | | | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT | | | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT | | | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED | | | SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED | | | CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS AN | | | EXPOSURE CATEGORY C AREA. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX | | | | | | JONATHAN N. BROOKS JR. | | | BUILDING PLAN REVIEWER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENTIAL SERVICES | | | |
|