| 2022-08-30 15:32:32 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080953 |
| | 8/30/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-2.0A: SUBMIT ENLARGED AND DIMENSIONED |
| | ARCHITECTURAL PLANS AND DETAILS FOR THE NEW OFFICE |
| | BATHROOM SHOWING COMPLIANCE WITH THE FBC ACC WHERE |
| | REQUIRED- SEC. 213.1 FBC ACC, & SECS. 107.2.1 & |
| | 107.3.5.1.3 WPB. DETAILS REQUIRED- |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SEC. 606.2. |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALLS- |
| | SEC. 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- SECTION 604.4 (SEE EXCEPTION 1). |
| | F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SEC. 606.3 (SEE EXCEPTION 1). |
| | G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE |
| | REFLECTIVE SURFACE- SEC. 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4. (SEE |
| | EXCEPTION 1). |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2 (SEE EXCEPTION 2). |
| | L) SHOWER WIDTH AND DEPTH DIMENSIONS- SEC. 608.2.2 |
| | M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTION 608.2.2.1 |
| | N) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3.2. (SEE SEC. |
| | 608.3 EXCEPTION 1). |
| | O) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SEC. 608.5.2. |
| | |
| | 2) P-2.0A: PROVIDE A SHOWER PAN DETAIL- SEC. 421.5.2 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |