| 2023-03-16 08:20:28 | 3RD REVIEW FMC |
| | PERMIT: 22080886 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) FIRST FLOOR BATH EXHAUST FAN SHOULD BE A MINIMUM OF |
| | 50 CFM. FRC TABLE M1506.2 |
| | |
| | 2) PROVIDE THE DUCT SIZES FOR ALL BATH EXHAUST FANS. |
| | FRC TABLE M1506.2 |
| | |
| | 3) THE RETURNS DO NOT SHOW ANY DUCTWORK. IS THE SPACE |
| | ABOVE THE CEILING TO BE A RETURN AIR PLENUM? IF SO, ADD |
| | A DETAIL DRAWING AND PROVIDE A NOTE ON THE DRAWINGS TO |
| | SHOW THIS OR SHOW THE RETURN AIR DUCTWORK SYSTEM. FRC |
| | M1601.1.1 NOTE 7.4 |
| | |
| | 4) PROVIDE THE DRYER DUCT MATERIAL, LENGTH, AND |
| | TERMINATION LOCATION. FRC M1502 |
| | |
| | 5) PROVIDE THE ANCHORAGE DETAIL FOR THE CONDENSING |
| | UNIT. FRC M1307.2 |
| | |
| | 6) PROVIDE THE CONDENSATE DISPOSAL PIPING AND |
| | TERMINATION LOCATION. FRC M1411.3 |
| | |
| | 7) PROVIDE THE TERMINATION LOCATION FOR THE KITCHEN |
| | HOOD EXHAUST. FRC M1506.3 |
| | |
| | 8) THE DESIGNER OF THE MECHANICAL SYSTEM WILL NEED TO |
| | DIGITALLY SIGN THE DOCUMENTS. FS 471/481 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |