| Notes |
| Date |
Text |
| 2022-09-30 08:20:51 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, | | | SUBMIT AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE | | | STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND | | | PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE | | | DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE | | | FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER | | | FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A | | | SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE DEVICES | | | IN THE PROJECT DOX PORTAL THAT YOU HAVE ACCESS TO. | | | PLEASE COMPLETE THIS DOCUMENT AND RESUBMIT. |
|