| 2023-01-13 17:08:44 | |
| | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080874 |
| | 1/3/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 3RD REQUEST FOR A PERMIT APPLICATION FOR THE |
| | OIL/SAND INTERCEPTOR TO BE SUBMITTED. THE APPLICATION |
| | SHALL NOT BE SUBMITTED UNDER THIS PERMIT BUT SEPARATELY |
| | AS THE YOU HAVE SUBMITTED THE BACKFLOW. AS PREVIOUSLY |
| | NOTED, I CANNOT APPROVE THE PLUMBING PLANS WITHOUT |
| | SUBMITTAL OF THE PERMIT APPLICATION FOR THE OIL |
| | INTERCEPTOR. BASED ON THE RESUBMITTED PLUMBING |
| | SPECIFYING A SEPARATE PERMIT APPLICATION FOR THE WATER |
| | REUSE SYSTEM AND RECLAIM TANKS, I CANNOT APPROVE THE |
| | PLANS WITHOUT SUBMITTAL OF THAT PERMIT APPLICATION. |
| | THIS WILL ENSURE THAT PERMIT ISSUANCE AND INSPECTIONS |
| | WILL BE DONE IN TIMELY AND ORDERLY MANNER. PLEASE SEE |
| | PREVIOUS COMMENT BELOW- |
| | |
| | PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE |
| | BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| | CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | 2) SHEETS P1, P4: PLEASE REVISE THE OIL/SAND ISOMETRIC |
| | DRAWING TO MATCH THE NEW PIPING LAYOUT SHOWN ON P1- |
| | SEC. 107.2.1 WPB. IT ALSO APPEARS THE LOCATIONS OF THE |
| | RECLAIM AND OIL DRAIN PIPES AND DRAIN PIPE SIZES ON |
| | SHEET 3.4 (TRENCH DRAIN CROSS SECTION) DO NOT MATCH |
| | WITH REVISED P1. |
| | |
| | 3) P1: SCH 80 PVC SPECIFIED FOR VACUUM PIPING ON THE |
| | SITE PLAN, HOWEVER THE SUBMITTED SHOP DRAWINGS SPECIFY |
| | SCH 40. PLEASE CLARIFY IF THE SYSTEM WILL BE PART OF |
| | THE MAIN PERMIT OR IF TO BE INSTALLED UNDER A SEPARATE |
| | PERMIT- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |