| 2022-09-21 13:55:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080874 |
| | 9/19/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 1.1 & P.1: SEPARATE PERMITS ARE REQUIRED FOR |
| | INSTALLATION OF THE POTABLE WATER BACKFLOW PREVENTER, |
| | THE EQUIPMENT WATER SERVICE BACKFLOW PREVENTER, |
| | OIL/SAND SEPARATOR, AND THE IRRIGATION SYSTEM- SECS. |
| | 105.1 & 107.2.1 WPB. |
| | |
| | PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE |
| | BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| | CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | 2) P.1 OIL/SAND SEPARATOR: A SEPARATE PERMIT, PLANS AND |
| | SPECIFICATIONS ARE REQUIRED HOWEVER A REVIEW OF THE |
| | SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. A) |
| | PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR |
| | INDICATING THE MANUFACTURER AND LISTING NUMBER AND |
| | SUBMIT SPECS FOR THE UNIT- SEC. 1003.4.2 FBC P. B) |
| | UNLISTED INTERCEPTORS SHALL COMPLY WITH SECS. |
| | 1003.2.4.1 & 1003.4.2.2. AND DETAILS SHALL BE PROVIDED |
| | INDICATING THE UNIT HAS A DEPTH OF 2 FT. BELOW THE |
| | INVERT, NOT LESS THAN AN 18-INCH WATER SEAL, AND SHALL |
| | HAVE A CAPACITY NOT LESS THAN 6 CU. FT. FOR THE FIRST |
| | 100 SQ. FT. OF AREA TO BE DRAINED PLUS 1 CU. FT. FOR |
| | EACH ADDITIONAL 100 SQ. FT. C) PLEASE PROVIDE AN |
| | ENLARGED PIPING AND INSTALLATION DIAGRAM SHOWING THE |
| | LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORT- SEC. |
| | 1003.9. D) PROVIDE INTERCEPTOR INSTALLATION DETAILS |
| | INCLUDING AN ELEVATION VIEW SHOWING THE BURIAL DEPTH, |
| | FOUNDATION BASE MATERIAL, AND BACKFILLING FOR SUPPORT |
| | AND STABILIZATION OF THE TANK. PLEASE CONTACT THE CITY |
| | OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL |
| | REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND |
| | GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065 |
| | OR 561-822-2274 OR EMAIL [email protected]. E) ALL SUBMITTALS |
| | SHALL BE APPROVED AND STAMPED BY THE DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE- SECTION 107.2.1, |
| | 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN ACCORDANCE |
| | WITH SECTION 107.3.4.1 WPB. |
| | |
| | 3) P.1: CAR WASH ONSITE WATER REUSE SYSTEM- SECS.1301 & |
| | 1302 FBC P. A) PROVIDE AN ISOMETRIC DRAWING SHOWING THE |
| | PIPING RUNS BETWEEN THE WASH BAY DRAINS TO THE TANKS, |
| | AND LOCATIONS OF PUMP, DRAINS, VENTS, CLEANOUTS AND |
| | MAKEUP WATER CONNECTION. B) PROVIDE STORAGE TANK AND |
| | TRAFFIC LID SPECIFICATIONS FROM THE MANUFACTURERS. C) |
| | PROVIDE TANK INSTALLATION DETAILS INCLUDING ELEVATION |
| | VIEWS SHOWING THE BURIAL DEPTH, FOUNDATION BASE |
| | MATERIALS AND BACKFILLING FOR SUPPORT. D) PROVIDE |
| | PIPING SPECIFICATIONS. E) ALL SUBMITTALS SHALL BE |
| | APPROVED AND STAMP BY THE DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE- SECTIONS 107.2.1 & 107.3.4. WPB. |
| | SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION |
| | 107.3.4.1 WPB. |
| | |
| | 4) P1, P.4 & P.5: PLEASE ADD THE WASHER AND WASHER |
| | EXTRACTOR TO THE EQUIPMENT SCHEDULE- SEC. 107.2.1 WPB. |
| | A) LINT INTERCEPTORS ARE REQUIRED FOR THE WASHER AND |
| | WASHER EXTRACTOR- SEC. 1003.6 FBC P. PLEASE ADD THE |
| | INTERCEPTORS TO THE EQUIPMENT SCHEDULE AND REVISE THE |
| | PLANS TO SHOW LOCATIONS AND PIPING DETAILS. |
| | |
| | 5) P.2 & P.4: A MEANS OF LIMITING THE HOT WATER |
| | DELIVERY TEMPERATURE FROM THE WASHING MACHINES AND MOP |
| | SINK SHALL BE PROVIDED IN ACCORDANCE WITH SEC. 607.1.1 |
| | FBC P. |
| | |
| | 6) P.2 & P.4: PLEASE PROVIDE SEPARATE LINE SYMBOLS TO |
| | DISTINGUISH HW AND HWR PIPING- SEC. 107.2.1 WPB. |
| | |
| | 7) P.5: REVISE THE WATER HEATER DETAIL TO SHOW THE |
| | LOCATIONS OF THE RECIRCULATION PUMP, HW RETURN LINE |
| | CONNECTIONS, AND THE DRAIN PAN LINE AND TERMINATION |
| | LOCATION- SECS. 607.2.1.2 & 504.7.1, 507.4.7.2 FBC P. |
| | |
| | 8) P.4 ROOF DRAINAGE: PROVIDE THE RAINFALL RATE USED AS |
| | THE BASIS OF THE CALCULATIONS- SEC. 1105.2 & 1106.1 FBC |
| | P. A) IT APPEARS WATER FROM THE UPPER ROOF WILL DRAIN |
| | ONTO THE MAIN ROOF. PLEASE ADD THE SQUARE FOOTAGE AND |
| | GPM FOR THE UPPER ROOF TO THE CALCULATIONS- SEC. |
| | 107.2.1 WPB. |
| | |
| | 9) SHEETS 3.1 & 3.3: REFER TO SECTIONS 306, 307, AND |
| | 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| | THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION |
| | 602.2 FBC ACC, AND SHOW THE LOCATIONS OF THE FOUNTAINS |
| | WILL BE IN COMPLIANCE WITH SECTION 307.2 PROTRUSION |
| | LIMITS. |
| | |
| | 10) SHEET 2.1 VACUUM AND COMPRESSED AIR SYSTEM A) |
| | PROVIDE PIPING LAYOUT DRAWINGS THAT SHOW THE TYPES AND |
| | SIZES OF VACUUM AND COMPRESSED AIR PIPINGS, AND THE |
| | PIPING RUNS. B) PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | VACUUM AND COMPRESSOR AND EQUIPMENT ANCHORING DETAILS- |
| | SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |