Plan Review Notes
Plan Review Notes For Permit 22080874
Permit Number 22080874
Review Stop P
Sequence Number 1
Notes
Date Text
2022-09-21 13:55:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080874
 9/19/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 1.1 & P.1: SEPARATE PERMITS ARE REQUIRED FOR
 INSTALLATION OF THE POTABLE WATER BACKFLOW PREVENTER,
 THE EQUIPMENT WATER SERVICE BACKFLOW PREVENTER,
 OIL/SAND SEPARATOR, AND THE IRRIGATION SYSTEM- SECS.
 105.1 & 107.2.1 WPB.
  
 PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) P.1 OIL/SAND SEPARATOR: A SEPARATE PERMIT, PLANS AND
 SPECIFICATIONS ARE REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR
 INDICATING THE MANUFACTURER AND LISTING NUMBER AND
 SUBMIT SPECS FOR THE UNIT- SEC. 1003.4.2 FBC P. B)
 UNLISTED INTERCEPTORS SHALL COMPLY WITH SECS.
 1003.2.4.1 & 1003.4.2.2. AND DETAILS SHALL BE PROVIDED
 INDICATING THE UNIT HAS A DEPTH OF 2 FT. BELOW THE
 INVERT, NOT LESS THAN AN 18-INCH WATER SEAL, AND SHALL
 HAVE A CAPACITY NOT LESS THAN 6 CU. FT. FOR THE FIRST
 100 SQ. FT. OF AREA TO BE DRAINED PLUS 1 CU. FT. FOR
 EACH ADDITIONAL 100 SQ. FT. C) PLEASE PROVIDE AN
 ENLARGED PIPING AND INSTALLATION DIAGRAM SHOWING THE
 LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORT- SEC.
 1003.9. D) PROVIDE INTERCEPTOR INSTALLATION DETAILS
 INCLUDING AN ELEVATION VIEW SHOWING THE BURIAL DEPTH,
 FOUNDATION BASE MATERIAL, AND BACKFILLING FOR SUPPORT
 AND STABILIZATION OF THE TANK. PLEASE CONTACT THE CITY
 OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL
 REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND
 GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065
 OR 561-822-2274 OR EMAIL [email protected]. E) ALL SUBMITTALS
 SHALL BE APPROVED AND STAMPED BY THE DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE- SECTION 107.2.1,
 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB.
  
 3) P.1: CAR WASH ONSITE WATER REUSE SYSTEM- SECS.1301 &
 1302 FBC P. A) PROVIDE AN ISOMETRIC DRAWING SHOWING THE
 PIPING RUNS BETWEEN THE WASH BAY DRAINS TO THE TANKS,
 AND LOCATIONS OF PUMP, DRAINS, VENTS, CLEANOUTS AND
 MAKEUP WATER CONNECTION. B) PROVIDE STORAGE TANK AND
 TRAFFIC LID SPECIFICATIONS FROM THE MANUFACTURERS. C)
 PROVIDE TANK INSTALLATION DETAILS INCLUDING ELEVATION
 VIEWS SHOWING THE BURIAL DEPTH, FOUNDATION BASE
 MATERIALS AND BACKFILLING FOR SUPPORT. D) PROVIDE
 PIPING SPECIFICATIONS. E) ALL SUBMITTALS SHALL BE
 APPROVED AND STAMP BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE- SECTIONS 107.2.1 & 107.3.4. WPB.
 SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION
 107.3.4.1 WPB.
  
 4) P1, P.4 & P.5: PLEASE ADD THE WASHER AND WASHER
 EXTRACTOR TO THE EQUIPMENT SCHEDULE- SEC. 107.2.1 WPB.
 A) LINT INTERCEPTORS ARE REQUIRED FOR THE WASHER AND
 WASHER EXTRACTOR- SEC. 1003.6 FBC P. PLEASE ADD THE
 INTERCEPTORS TO THE EQUIPMENT SCHEDULE AND REVISE THE
 PLANS TO SHOW LOCATIONS AND PIPING DETAILS.
  
 5) P.2 & P.4: A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE FROM THE WASHING MACHINES AND MOP
 SINK SHALL BE PROVIDED IN ACCORDANCE WITH SEC. 607.1.1
 FBC P.
  
 6) P.2 & P.4: PLEASE PROVIDE SEPARATE LINE SYMBOLS TO
 DISTINGUISH HW AND HWR PIPING- SEC. 107.2.1 WPB.
  
 7) P.5: REVISE THE WATER HEATER DETAIL TO SHOW THE
 LOCATIONS OF THE RECIRCULATION PUMP, HW RETURN LINE
 CONNECTIONS, AND THE DRAIN PAN LINE AND TERMINATION
 LOCATION- SECS. 607.2.1.2 & 504.7.1, 507.4.7.2 FBC P.
  
 8) P.4 ROOF DRAINAGE: PROVIDE THE RAINFALL RATE USED AS
 THE BASIS OF THE CALCULATIONS- SEC. 1105.2 & 1106.1 FBC
 P. A) IT APPEARS WATER FROM THE UPPER ROOF WILL DRAIN
 ONTO THE MAIN ROOF. PLEASE ADD THE SQUARE FOOTAGE AND
 GPM FOR THE UPPER ROOF TO THE CALCULATIONS- SEC.
 107.2.1 WPB.
  
 9) SHEETS 3.1 & 3.3: REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW THE LOCATIONS OF THE FOUNTAINS
 WILL BE IN COMPLIANCE WITH SECTION 307.2 PROTRUSION
 LIMITS.
  
 10) SHEET 2.1 VACUUM AND COMPRESSED AIR SYSTEM A)
 PROVIDE PIPING LAYOUT DRAWINGS THAT SHOW THE TYPES AND
 SIZES OF VACUUM AND COMPRESSED AIR PIPINGS, AND THE
 PIPING RUNS. B) PROVIDE EQUIPMENT SCHEDULES FOR THE
 VACUUM AND COMPRESSOR AND EQUIPMENT ANCHORING DETAILS-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  