| 2022-11-28 13:35:31 | ELECTRIC REVIEW FAILED |
| | 1) ELECTRIC RISER DIAGRAM DETAILS (2) ELECTRIC PANELS |
| | FOR WHAT IS ASSUMED TO BE THE MAIN HOUSE. THESE PANELS |
| | ARE DETAILED AS BEING FED WITH 2/0 CU CONDUCTORS. 2/0 |
| | CU CONDUCTORS FEEDING ONLY PART OF THE MAIN HOUSE ARE |
| | NOT PERMITTED TO BE DE-RATED TO 83%. ONLY CONDUCTORS |
| | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A DWELLING IS |
| | PERMITTED TO BE DE-RATED TO 83%. IN ADDITION, ALL 6 OF |
| | THESE CONDUCTORS ARE DETAILED AS BEING IN THE SAME |
| | CONDUIT WHICH WOULD REQUIRE FURTHER DERATING AS PER NEC |
| | 310.15(B)(3). PLEASE CORRECT AS APPLICABLE FOR CODE |
| | COMPLIANCE |
| | 2) THE ELECTRIC RISER DIAGRAM DOES NOT DETAIL SIZE OF |
| | SERVICE OR ANY MAIN DISCONNECTS. PLEASE DETAIL SERVICE |
| | SIZE AND ALL MAIN OVERCURRENT PROTECTION AS REQUIRED |
| | PER NEC 215.5 AND NEC 240.4 |
| | 3) PLEASE DETAIL ALL MAIN DISCONNECTS AS GROUPED IN ONE |
| | LOCATION AND MARKED TO INDICATE THE LOAD SERVED AS PER |
| | NEC 230.72 |
| | 4) PLEASE DETAIL GROUNDING ELECTRODE CONNECTIONS IN |
| | PROPER LOCATIONS NOT CONNECTED TO CONDUITS. NEC215.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |