| 2022-11-04 09:55:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET CVR - THERE IS AN INDICATION OF A NEW WOOD |
| | FLOOR OVER EXISTING SANDED FLOOR. |
| | |
| | FOR CLARIFICATION PURPOSES, PLEASE PROVIDE A FLOOR |
| | PRODUCT NAME AND TYPE FOR THE ACTUAL PROPOSED FLOORING |
| | AND IF IT IS GOING TO BE PLAVED OVER THE EXISTING FLOOR |
| | WITH AN ADDITIONAL LAYER OF UNDERLAYMNET. |
| | |
| | |
| | |
| | 2) SHEET A 1 - THERE IS AN INDICATION OF THE SPEC SHEET |
| | FOR THE FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A |
| | PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING. |
| | |
| | FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL |
| | ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| | THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, OR WHOLE WOOD |
| | PLANKS A PRODUCT SPEC SHEETS WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |