| Plan Review Notes For Permit 22080820 |
| Permit Number |
22080820 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2023-02-14 16:00:50 | 1ST REVIEW FMC | | | PERMIT: 22080820 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATIONS FOR THESE WAREHOUSES DO NOT | | | REFLECT WHAT IS SHOWN ON THE M-1 SHEET. THE UNIT 432 | | | HAS AN A/C LOAD OF 41,932 BUT THE DRAWING INDICATES 2 5 | | | TON UNITS. EXPLAIN WHY THE 2 5 TON UNITS. | | | FEC C403.2.2 | | | | | | 2) UNIT 434 ENERGY CALC CALLS FOR 41,683 OF COOLING BUT | | | THE M-1 DRAWING INDICATES 2 3-TON UNITS. EXPLAIN WHY | | | THE 2 3 - TON UNITS. FEC C403.2.2 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|