Plan Review Notes
Plan Review Notes For Permit 22080820
Permit Number 22080820
Review Stop B
Sequence Number 3
Notes
Date Text
2023-01-12 13:11:07RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE WIND DESIGN DATA USED (WIND SPEED,
 RISK CATEGORY, EXPOSURE, ETC.) FOR WIND DESIGN - SEE
 FBC 1603.1.4
  
 2) DOOR SIZE HAS NOT CHANGED ON THE DOOR SCHEDULE -
 PIVOT DOOR PRODUCT APPROVAL SEE PAGE 3 OF 11 (NOTE:
 DOOR CANNOT BE USED AS AN EGRESS DOOR WHEN THE DOOR
 LEAF WIDTH IS MORE THAN 48") -- THE 6 FOOT WIDE ENTRY
 DOOR SHOWN DOES NOT COMPLY WITH FBC 1010.1.1 SIZE OF
 DOORS. THE MAXIMUM WIDTH OF A SWINGING DOOR LEAF SHALL
 BE 48 INCHES (1219 MM) NOMINAL
  
 3) SHOW THE OCCUPANCY CLASSIFICATION ON THE DRAWINGS AS
 (S1) OR (S2) - - PLEASE SHOW THE MAIN "USE" FOR EACH
 BUILDING ( RESTAURANT, PROFESSIONAL OFFICES, STORAGE
 (WHAT MATERIALS OF STORAGE), RETAIL OR WHOLESALE STORE
 ETC.) - A WAREHOUSE WOULD BE A STORAGE AREA PLEASE SEE
 FBC SECTION 311 AND SHOW THE OCCUPANCY CLASSIFICATION
 AS S1 OR S2 - THE OCCUPANCY CLASSIFICATION NEEDS TO BE
 DETERMINED - FBC 302.1 OCCUPANCY CLASSIFICATION.
 OCCUPANCY CLASSIFICATION IS THE FORMAL DESIGNATION OF
 THE PRIMARY PURPOSE OF THE BUILDING, STRUCTURE OR
 PORTION THEREOF. STRUCTURES SHALL BE CLASSIFIED INTO
 ONE OR MORE OF THE OCCUPANCY GROUPS LISTED IN THIS
 SECTION BASED ON THE NATURE OF THE HAZARDS AND RISKS TO
 BUILDING OCCUPANTS GENERALLY ASSOCIATED WITH THE
 INTENDED PURPOSE OF THE BUILDING OR STRUCTURE.
  
  