| 2023-01-12 13:11:07 | RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE WIND DESIGN DATA USED (WIND SPEED, |
| | RISK CATEGORY, EXPOSURE, ETC.) FOR WIND DESIGN - SEE |
| | FBC 1603.1.4 |
| | |
| | 2) DOOR SIZE HAS NOT CHANGED ON THE DOOR SCHEDULE - |
| | PIVOT DOOR PRODUCT APPROVAL SEE PAGE 3 OF 11 (NOTE: |
| | DOOR CANNOT BE USED AS AN EGRESS DOOR WHEN THE DOOR |
| | LEAF WIDTH IS MORE THAN 48") -- THE 6 FOOT WIDE ENTRY |
| | DOOR SHOWN DOES NOT COMPLY WITH FBC 1010.1.1 SIZE OF |
| | DOORS. THE MAXIMUM WIDTH OF A SWINGING DOOR LEAF SHALL |
| | BE 48 INCHES (1219 MM) NOMINAL |
| | |
| | 3) SHOW THE OCCUPANCY CLASSIFICATION ON THE DRAWINGS AS |
| | (S1) OR (S2) - - PLEASE SHOW THE MAIN "USE" FOR EACH |
| | BUILDING ( RESTAURANT, PROFESSIONAL OFFICES, STORAGE |
| | (WHAT MATERIALS OF STORAGE), RETAIL OR WHOLESALE STORE |
| | ETC.) - A WAREHOUSE WOULD BE A STORAGE AREA PLEASE SEE |
| | FBC SECTION 311 AND SHOW THE OCCUPANCY CLASSIFICATION |
| | AS S1 OR S2 - THE OCCUPANCY CLASSIFICATION NEEDS TO BE |
| | DETERMINED - FBC 302.1 OCCUPANCY CLASSIFICATION. |
| | OCCUPANCY CLASSIFICATION IS THE FORMAL DESIGNATION OF |
| | THE PRIMARY PURPOSE OF THE BUILDING, STRUCTURE OR |
| | PORTION THEREOF. STRUCTURES SHALL BE CLASSIFIED INTO |
| | ONE OR MORE OF THE OCCUPANCY GROUPS LISTED IN THIS |
| | SECTION BASED ON THE NATURE OF THE HAZARDS AND RISKS TO |
| | BUILDING OCCUPANTS GENERALLY ASSOCIATED WITH THE |
| | INTENDED PURPOSE OF THE BUILDING OR STRUCTURE. |
| | |
| | |