| Plan Review Notes For Permit 22080820 |
| Permit Number |
22080820 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-13 16:33:53 | 2ND REVIEW FMC | | | PERMIT: 22080820 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE | | | MISSING. THE REFERENCED NEW INFORMATION ON SHEET M-1 IS | | | THE OUTDOOR AIR CALCULATIONS. | | | | | | 2) THE ENERGY CALCULATIONS DO NOT SHOW THE DOORS. | | | PLEASE PROVIDE ENERGY CALCULATIONS AND MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS THAT INCLUDE THE DOORS. | | | FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|