2022-09-14 10:26:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080820 432 25TH ST
  
 1ST REVIEW
  
 GENERAL: ELECTRONIC SIGNATURES ARE NOT VALID.
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 ***A) A-3/DETAILS 2&3: PER FBC ACC 609.4, GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP (NOT THE CENTER) OF THE GRIPPING
 SURFACE
 ***B) A-3/DETAIL 7: PER FBC ACC 603.3, PLEASE CLEARLY
 SHOW ON PLANS THE 40 INCH DIMENSION IS TO THE
 REFLECTING SURFACE OF THE MIRROR.
 ***C) PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL FOR
 DRINKING FOUNTAIN(S); SHOW COMPLIANCE WITH FBC 306.2,
 306.3, 602.3, 602.4, 602.5 AND 602.7.
 ***D) PER FBC ACC 602.1, DRINKING FOUNTAIN(S) SHALL
 COMPLY WITH FBC ACC 307.2 FOR PROTRUDING OBJECTS
  
 2. PER WPB FBC 107.2.1, PROVIDE WALL FINISHES FOR THE
 TOILET ROOMS AND FOR THE MOP SINK. COMPLY WITH FBC PL
 310.3 AND FBC 1210.2.2; WALLS AND PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 NOT LESS THAN 4 FEET ABOVE THE FLOOR. SECTION 1210.2.2
 STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF
 THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD
 NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE
 MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY
 CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHERE
 COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 3. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(3)(13),
 PROVIDE A WATER DISTRIBUTION PLAN, A SIZED WATER RISER
 DIAGRAM AND SIZING CALCULATIONS.
 ***A) IDENTIFY POINTS OF CONNECTION TO FIXTURES AND
 EQUIPMENT.
 ***B) SHOW AND IDENTIFY WATER HAMMER ARRESTORS.
 ***C) SHOW ALL IN-LINE VALVES AS REQUIRED BY FBC PL
 606.1.
 ***D) SHOW ON THE FLOOR PLAN THE LOCATION OF THE WATER
 HEATER
 ***D) SHOW ALL BACKFLOW PREVENTERS
 ***E) PLAN SHEET A-0/PLUMBING NOTES CALL FOR EXTENDING
 WATER SERVICE TO METER, PROVIDE METER AND SHUT OFF
 VALVE IN BOX OUTSIDE OF THE BUILDING. A BACKFLOW
 PREVENTER IS REQUIRED PER FBC PL 608.1. IF THERE IS AN
 EXISTING BACKFLOW PREVENTER IN PLACE, THEN SHOW IT ON
 THE PLAN AS EXISTING.
 IF THIS REQUIRES A NEW CONNECTION TO THE CITY UTILITIES
 THEN PROVIDE A DETAIL AND A SCHEDULE. A SEPARATE PERMIT
 WILL BE REQUIRED TO BE SUBMITTED AND APPROVED PRIOR TO
 ISSUANCE OF THE PRIMARY PERMIT.
  
 4. PER WPB FBC 107.2.1, FBC PL 419.5 AND FBC PL
 607.1.2, PROVIDE IN THE SCHEDULE, AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE FOR THE SCHEDULED
 LAVATORIES THAT CONFORMS TO ASSE 1070 OR CSA B125.3
  
 5. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(5),
 PROVIDE THE ELECTRICAL CHARACTERISTICS FOR THE
 SCHEDULED WATER HEATER. COORDINATE WITH THE ELECTRICAL
 PLANS.
  
 6. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(5),
 PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY WITH
 FBC EC TABLE C404.2
  
 7. P-1/SANITARY RISER DIAGRAM: PER WPB FBC 107.2.1 AND
 WPB FBC 107.3.5.1.3(4)(13), PROVIDE SIZING OF ALL
 SEGMENTS OF SANITARY DRAIN AND VENT PIPING.
  
 8. P-1/SANITARY RISER DIAGRAM: PER FBC PL 901.2.1,
 PROVIDE A VENT FOR THE DRINKING FOUNTAIN.
  
 9. P-1/SANITARY RISER DIAGRAM: PER FBC PL 914.2,
 PROVIDE A DRY VERTICAL VENT BETWEEN THE TWO WATER
 CLOSETS.
  
 10. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1 AND SHALL BE
 ON SITE PRIOR TO FINAL INSPECTION.
  
 11. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION SPEC FOR HOT WATER INSULATION COMPLY WITH
 FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:
  
 12. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 13. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 14. PER WPB FBC 107.2.1, PROVIDE NOTE STATING "SEE
 A-0/PLUMBING NOTES FOR WATER AND SANITARY MATERIAL
 SPECIFICATIONS".
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  
  