Plan Review Notes
Plan Review Notes For Permit 22080820
Permit Number 22080820
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-22 14:00:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.2 - THERE IS AN INDICATION OF A MERCANTILE
 OCCUPANCY; HOWEVER, THERE IS ALSO AN INDICATION IN BLDG
 434, OF A NEW STORAGE AREA THAT IS SEPARATED BY A
 NONRATED NON ACCESSIBLE WALL & WINDOW.
  
 A STORAGE OCCUPACNY IS NOT THE SAME OCCUPANCY
 CLASSIFICATION AS MERCANTILE.
  
 PER NFPA 101 CH 6, TABLE 6.1.14.4.1, A 2 HOUR FIRE
 SEPARATION IS REQUIRED.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFIY WITH SPECIFIC
 DETAILS AND NARRATIVE AND FIRE CODE REFERENCES.
  
  
 1A) SHOULD THIS BE CONSIDERED AS A MIXED NON-SEPARATED
 OCCUPANCY CLASSIFICATION PLEASE REVIEW AND CORRECT AS
 APPLICABLE.
  
  
  
 2) ON REVIEW OF THE ABOVE COMMENTS, A STORAGE OCCUPANCY
 NON-SEOARATED OR STAND ALONE SHALL HAVE THE HAZARD OF
 CONTENTS REVIEWED FOR FIRE RATED SEPARATION PURPOSES.
  
 PER NFPA 101
  
 6.2 HAZARD OF CONTENTS
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE
 THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF SMOKE
 OR GASES GENERATED, AND THE DANGER OF EXPLOSION OR
 OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE
 BUILDING OR STRUCTURE
  
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED DESIGN
 PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE
 AUTHORITY HAVING
 JURISDICTION FOR REVIEW AND APPROVAL ON THE BASIS OF
 THE CHARACTER OF THE
 CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED IN
 THE BUILDING OR
 STRUCTURE.
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD
 OF CONTENTS EXIST IN DIFFERENT PARTS OF A BUILDING OR
 STRUCTURE, THE MOST
 HAZARDOUS SHALL GOVERN THE CLASSIFICATION, UNLESS
 HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE
 SECTIONS OF CHAPTERS 11 THROUGH 43
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR STRUCTURE
 SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH IN
 ACCORDANCE WITH 6.2.2.2,
 6.2.2.3, AND 6.2.2.4
  
 PLEASE PROVIDE DETAILS FO THE PROPOSED
 PRODUCT/COMMODITY BEING STORED.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  