| 2022-08-22 14:00:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A 1.2 - THERE IS AN INDICATION OF A MERCANTILE |
| | OCCUPANCY; HOWEVER, THERE IS ALSO AN INDICATION IN BLDG |
| | 434, OF A NEW STORAGE AREA THAT IS SEPARATED BY A |
| | NONRATED NON ACCESSIBLE WALL & WINDOW. |
| | |
| | A STORAGE OCCUPACNY IS NOT THE SAME OCCUPANCY |
| | CLASSIFICATION AS MERCANTILE. |
| | |
| | PER NFPA 101 CH 6, TABLE 6.1.14.4.1, A 2 HOUR FIRE |
| | SEPARATION IS REQUIRED. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFIY WITH SPECIFIC |
| | DETAILS AND NARRATIVE AND FIRE CODE REFERENCES. |
| | |
| | |
| | 1A) SHOULD THIS BE CONSIDERED AS A MIXED NON-SEPARATED |
| | OCCUPANCY CLASSIFICATION PLEASE REVIEW AND CORRECT AS |
| | APPLICABLE. |
| | |
| | |
| | |
| | 2) ON REVIEW OF THE ABOVE COMMENTS, A STORAGE OCCUPANCY |
| | NON-SEOARATED OR STAND ALONE SHALL HAVE THE HAZARD OF |
| | CONTENTS REVIEWED FOR FIRE RATED SEPARATION PURPOSES. |
| | |
| | PER NFPA 101 |
| | |
| | 6.2 HAZARD OF CONTENTS |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL BE |
| | THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF SMOKE |
| | OR GASES GENERATED, AND THE DANGER OF EXPLOSION OR |
| | OTHER OCCURRENCE |
| | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE |
| | OCCUPANTS OF THE |
| | BUILDING OR STRUCTURE |
| | |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED DESIGN |
| | PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING |
| | JURISDICTION FOR REVIEW AND APPROVAL ON THE BASIS OF |
| | THE CHARACTER OF THE |
| | CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED IN |
| | THE BUILDING OR |
| | STRUCTURE. |
| | |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF HAZARD |
| | OF CONTENTS EXIST IN DIFFERENT PARTS OF A BUILDING OR |
| | STRUCTURE, THE MOST |
| | HAZARDOUS SHALL GOVERN THE CLASSIFICATION, UNLESS |
| | HAZARDOUS AREAS ARE |
| | SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND |
| | THE APPLICABLE |
| | SECTIONS OF CHAPTERS 11 THROUGH 43 |
| | |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR STRUCTURE |
| | SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH IN |
| | ACCORDANCE WITH 6.2.2.2, |
| | 6.2.2.3, AND 6.2.2.4 |
| | |
| | PLEASE PROVIDE DETAILS FO THE PROPOSED |
| | PRODUCT/COMMODITY BEING STORED. |
| | |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |