| 2022-10-06 08:48:00 | RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS. |
| | ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE DESIGNER OF RECORD OR BE SHOWN ON THE |
| | PLANS BY PRODUCT APPROVAL NUMBER _ FBC WPB 107.3.4 |
| | |
| | 2) THE OCCUPANT LOAD SHOWN ON DRAWING CVR UNDER |
| | "OCCUPANCY LOADS" SHOWS THE INCORRECT NUMBER OF |
| | OCCUPANTS FOR MERCANTILE - SEE FBC TABLE 1004.5 |
| | |
| | 3) PLEASE SHOW THE OCCUPANT LOAD FOR EACH BUILDING |
| | SEPARATELY. |
| | |
| | 4) PLEASE SHOW THE SQUARE FOOTAGE FOR EACH BUILDING |
| | SEPARATELY. |
| | |
| | 5) PLEASE SHOW THE WALL LOCATION DIMENSIONS FOR ALL |
| | RESTROOM AND OFFICE WALLS. |
| | |
| | 6) PLEASE SHOW THE WIND DESIGN DATA USED FOR WIND |
| | DESIGN PER FBC 1603.1.4 |
| | |
| | 7) THE 6 FOOT WIDE ENTRY DOOR SHOWN DOES NOT COMPLY |
| | WITH FBC 1010.1.1 SIZE OF DOORS. THE MAXIMUM WIDTH OF A |
| | SWINGING DOOR LEAF SHALL BE 48 INCHES (1219 MM) |
| | NOMINAL. |
| | |
| | 8) PLEASE SHOW THE RAMP SLOPE - FBC 405.2 SLOPE. RAMP |
| | RUNS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12. |
| | |
| | 9) PLEASE SHOW THE STEEL COLUMN CONNECTION TO THE ADDED |
| | TIEBEAM. |
| | |
| | 10) PLEASE SHOW THE RESTROOM WALL FINISH - FBC 1210.2.2 |
| | WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR,( DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 11) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET GRAB |
| | BAR MAXIMUM HEIGHT TO THE TOP OF THE GRIPPING SURFACE - |
| | FBC A 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | |
| | 12) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| | "REFLECTING SURFACE" WHEN REFERRING TO THE MIRROR |
| | LOCATION - FBC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 13) SEPARATE PERMITS ARE REQUIRED FOR SEPARATE |
| | BUILDINGS. |
| | |
| | 14) ALL SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | PROJECTDOX - SIGNED AND SEALED DRAWINGS IN PROJECTDOX |
| | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED |
| | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |