Plan Review Notes
Plan Review Notes For Permit 22080820
Permit Number 22080820
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-06 08:48:00RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS.
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD OR BE SHOWN ON THE
 PLANS BY PRODUCT APPROVAL NUMBER _ FBC WPB 107.3.4
  
 2) THE OCCUPANT LOAD SHOWN ON DRAWING CVR UNDER
 "OCCUPANCY LOADS" SHOWS THE INCORRECT NUMBER OF
 OCCUPANTS FOR MERCANTILE - SEE FBC TABLE 1004.5
  
 3) PLEASE SHOW THE OCCUPANT LOAD FOR EACH BUILDING
 SEPARATELY.
  
 4) PLEASE SHOW THE SQUARE FOOTAGE FOR EACH BUILDING
 SEPARATELY.
  
 5) PLEASE SHOW THE WALL LOCATION DIMENSIONS FOR ALL
 RESTROOM AND OFFICE WALLS.
  
 6) PLEASE SHOW THE WIND DESIGN DATA USED FOR WIND
 DESIGN PER FBC 1603.1.4
  
 7) THE 6 FOOT WIDE ENTRY DOOR SHOWN DOES NOT COMPLY
 WITH FBC 1010.1.1 SIZE OF DOORS. THE MAXIMUM WIDTH OF A
 SWINGING DOOR LEAF SHALL BE 48 INCHES (1219 MM)
 NOMINAL.
  
 8) PLEASE SHOW THE RAMP SLOPE - FBC 405.2 SLOPE. RAMP
 RUNS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12.
  
 9) PLEASE SHOW THE STEEL COLUMN CONNECTION TO THE ADDED
 TIEBEAM.
  
 10) PLEASE SHOW THE RESTROOM WALL FINISH - FBC 1210.2.2
 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,( DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 11) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET GRAB
 BAR MAXIMUM HEIGHT TO THE TOP OF THE GRIPPING SURFACE -
 FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 12) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTING SURFACE" WHEN REFERRING TO THE MIRROR
 LOCATION - FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 13) SEPARATE PERMITS ARE REQUIRED FOR SEPARATE
 BUILDINGS.
  
 14) ALL SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).