| Plan Review Notes For Permit 22080789 |
| Permit Number |
22080789 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-26 16:34:12 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22080789 | | | 8/26/22 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR | | | INSTALLATION OF THE GENERATOR- SEC. 105.1 & 107.2.1 | | | WPB. AN ELECTRICAL CONTRACTOR SHALL SUBMIT A PERMIT | | | APPLICATION AND COMPLETE PLANS AND SPECIFICATIONS FOR | | | THE GENERATOR INSTALLATION. | | | | | | 2) PLEASE PROVIDE THE INCREASE IN VALUE FOR | | | INSTALLATION OF THE GAS PIPING THAT INCLUDES LABOR AND | | | MATERIALS- SEC. 109.3 WPB. | | | | | | 3) SHEETS FG-000, FG-001, & FG-002: THE 2-INCH PE PIPE | | | IS UNDERSIZED BASED ON TABLE 402.4(21) FBC FG SPECIFIED | | | ON SHEET FG-000. USING THE LONGEST LENGTH METHOD- SEC. | | | 402.4.1 FBC FG, THE 2-INCH PIPE IS LIMITED TO 661000 | | | BTUS AT ESTIMATED 117 TDL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|