| Plan Review Notes For Permit 22080757 |
| Permit Number |
22080757 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-06 11:44:43 | GAS PLANS AND PERMIT UNDER 22051342 | | 2022-10-04 09:27:58 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22080757 | | | 10/4/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A GAS PIPING LAYOUT PLAN AND ISOMETRIC | | | DRAWING- SEC. 107.3.5.3 WPB. PLEASE NOTE THE ISOMETRIC | | | DRAWING SHALL INDICATE- | | | | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | K) PIPE SIZING TABLES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|