| Plan Review Notes For Permit 22080743 |
| Permit Number |
22080743 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-19 11:00:44 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN | | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | | FIRE RESCUE. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR | | | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS | | | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF | | | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT | | | ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS | | | AFFIXED TO THE DOOR LEAF. | | | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. | | | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE | | | HAND IN THE DIRECTION OF EGRESS. | | | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER | | | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE | | | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. | | | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE | | | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE | | | DIRECTION OF EGRESS. | | | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN | | | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS | | | CONTROL SYSTEM UNITS. | | | | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|