 MECHANICAL REVIEW DENIED:
  
 FBC M TABLE 403.3.1.1, THE CONFERENCE ROOMS (FCU-2N-4 &
 FCU-2N-6) ON THE VENTILATION REQUIREMENT SCHEDULE DO
 NOT COMPLY WITH TABLE 403.3.1.1 AS THE NUMBER OF
 PEOPLE, CALCULATED BY THE TABLE, RESULTS IN HIGHER CFM
 REQUIREMENTS THAN LISTED ON THE VENTILATION REQUIREMENT
 SCHEDULE OF SHEET M6.0.1.
  