2022-10-06 14:24:551ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SUPPLIED
 DOES NOT REPRESENT ACTUAL PLUMBING. ON THE SECOND
 FLOOR, THE SHOWER CONNECTS TO THE RISER ABOVE THE
 LAVATORY FIXTURE DRAIN?
  
 2. 2020 FRC P3108.1 - DOWNSTAIRS BATHROOM - THE TUB AND
 WATER CLOSET CONNECT UPSTREAM OF THE VENTED FIXTURE
 CONNECTION AND ONLY ONE TRAPPED FIXTURE IS ALLOWED
 UPSTREAM.
  
 3. 2017 WPB AMEND 107.2.1 - ALSO, THERE ARE 4 WATER
 CLOSETS SHOWN ON THE DIAGRAM AND ONLY 3 WATER CLOSETS
 ON THE FLOOR PLAN. PLEASE CORRECT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR