Plan Review Notes
Plan Review Notes For Permit 22080669
Permit Number 22080669
Review Stop E
Sequence Number 1
Notes
Date Text
2022-10-18 13:09:21ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL ALL THE OUTSIDE RECEPTACLES AS
 REQUIRED PER NEC 210.52(E), 210.63 AND 210.64
 2) PLEASE NUMBER THE A/C MINI SPLIT UNITS AND THERE
 ASSOCIATED CONDENSERS. FBC 107.2
 3) PLEASE DETAIL THE SECOND FLOOR SMOKE ALARM AS A
 COMBINATION CARBON MONOXIDE AND SMOKE ALARM AS REQUIRED
 PER FBC R 315.1
 4) PLEASE DETAIL HOW OUTDOOR FLOOD LIGHTS ARE
 CONTROLLED. FBC 107.2
 5) PLEASE LOCATE AIR HANDLER AND COMPRESSOR, LISTED IN
 PANEL SCHEDULE, ON ELECTRIC FLOOR PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  