| 2022-11-17 14:01:03 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080650 |
| | 11/17/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #3 FROM THE |
| | 1ST REVIEW ARE LISTED BELOW. PLEASE REVIEW THE COMMENT |
| | AND CONTACT ME IF YOU HAVE ANY QUESTIONS. |
| | |
| | 3) P1.1: THE PLUMBING ALTERATIONS INCLUDING THE GREASE |
| | INTERCEPTOR ARE BEING REVIEWED UNDER THIS MASTER PERMIT |
| | HOWEVER A SEPARATE PERMIT AND PLANS IS REQUIRED FOR |
| | INSTALLATION OF THE GREASE INTERCEPTOR- SECS. 105.1 & |
| | 107.2.1 WPB. |
| | PLEASE NOTE: DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO |
| | ISSUANCE OF THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN |
| | SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU |
| | DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | PLEASE NOTE THE FOLLOWING PLAN REVIEW SUBMITTAL |
| | REQUIREMENTS FOR THE INTERCEPTOR- SECS. 1003.1- |
| | 1003.3.8 FBC P. |
| | A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | GUIDELINES- SECS.1003.3.5 OR 1003.3.7 FBC P. |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND |
| | CAPACITY OF THE UNIT. |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101 FOR HYDROMECHANICAL TYPES. |
| | D) FLOOR PLAN DRAWING SHOWING THE LOCATION OF THE UNIT |
| | AND ELEVATION DETAIL |
| | E) PIPING DIAGRAM INCLUDING LOCATIONS AND SIZES OF |
| | INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL VENTS, AND |
| | SAMPLING PORTS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |