| 2022-08-26 08:38:15 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080650 |
| | 8/26/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-1 & P1.1: THE PLANS AND PHOTOS INDICATE THE |
| | PROJECT IS PLUMBING PREP WORK FOR A NEW BUSINESS- SIVA |
| | CAFE. THE PREVIOUS BUSINESS AT THE LOCATION WAS |
| | WANDERER BRACELETS WHICH COMPLETED AN INTERIOR REMODEL |
| | UNDER PERMIT 16061686. PLEASE REFER TO SEC. 1001.1 FBC |
| | EXISTING BUILDING CODE-2020 AND PROVIDE CODE DATA ON |
| | THE PLAN INCLUDING COMPLIANCE AS EITHER A CHANGE OF |
| | OCCUPANCY OR CHANGE OF USE. |
| | |
| | 2) A-1 & P1.1: REFER TO SEC. 1010.1 FBC EX AND PROVIDE |
| | PLUMBING FIXTURE CALCULATIONS FOR THE NEW TENANT SPACE |
| | IN ACCORDANCE WITH TABLE 403.1 FBC P. SHOW THE REQUIRED |
| | AND PROVIDED NUMBER OF FIXTURES BASED ON THE OCCUPANCY |
| | AND USE OF THE SPACE. |
| | |
| | 3) P1.1: THE PLUMBING ALTERATIONS INCLUDING THE GREASE |
| | INTERCEPTOR ARE BEING REVIEWED UNDER THIS MASTER PERMIT |
| | HOWEVER A SEPARATE PERMIT AND PLANS IS REQUIRED FOR |
| | INSTALLATION OF THE GREASE INTERCEPTOR- SECS. 105.1 & |
| | 107.2.1 WPB. PLEASE NOTE: DUE TO A CHANGE IN PROCESS, |
| | THE GREASE INTERCEPTOR PERMIT IS REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION ?TBD? (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 4) P1.1: PROVIDE A PLUMBING FIXTURE SCHEDULE ON THE |
| | PLAN INDICATING THE MAKES AND MODELS OF THE |
| | 3-COMPARTMENT SINK, GREASE INTERCEPTOR, THE HAND SINK, |
| | WATER PURIFICATION SINK, FLOOR SINK, FILTRATION SYSTEM, |
| | AND SINK FAUCETS- SEC. 107.3.5.1.3 WPB. |
| | |
| | 5) P1.1: PROVIDE A WATER SUPPLY PLAN OR WATER RISER- |
| | SEC. 107.3.5.1.3 WPB. PLEASE INCLUDE WATER LINES TO |
| | FIXTURES AND APPLIANCES INCLUDING THE DISHWASHER, |
| | BEVERAGE AND COFFEE MACHINES. |
| | |
| | 6) P1.1: THE SANITARY ISOMETRIC DOES NOT SHOW THE |
| | PIPING CONNECTIONS TO THE GREASE INTERCEPTOR AND THE |
| | DISHWASHER- SEC. 107.3.5.1.3 WPB. |
| | |
| | 7) PLEASE PROVIDE AN ENLARGED PIPING DETAIL SHOWING THE |
| | CONNECTIONS FROM THE 3-COMPARTMENT SINK TO THE GREASE |
| | INTERCEPTOR- SECS. 802.1.1 & 1003.3.5 FBC P. |
| | |
| | 8) P1.1: PROVIDE SIZING CALCULATIONS ON THE PLAN FOR |
| | THE INTERCEPTOR- SEC. 1003.3.5.1 FBC P. |
| | |
| | 9) P1.1: THE DRAINAGE FROM THE MOP SINK SHALL DISCHARGE |
| | INTO THE GREASE WASTE LINE AND INTERCEPTOR- SEC. |
| | 1003.3.1 FBC P. THE ISOMETRIC SHOWS THE DRAIN |
| | CONNECTING TO THE SANITARY LINE. |
| | |
| | 10) P1.1 NOTE 3: THE NOTE AND PHOTOS APPEAR TO SHOW THE |
| | MOP SINK AND WATER HEATER HAVE BEEN RELOCATED FROM |
| | THEIR ORIGINAL LOCATIONS UNDER PERMIT- 16061686. PLEASE |
| | MODIFY THE SCOPE OF WORK AND DRAWINGS ACCORDINGLY- SEC. |
| | 107.2.1 WPB. PLEASE NOTE THE WATER HEATER APPROVED |
| | UNDER PERMIT 16061686 WAS A 40-GALLON LOCHNIVAR. THE |
| | PHOTOS INDICATE AN AO SMITH WHICH APPEARS TO BE NEW- |
| | PLEASE CLARIFY. |
| | |
| | 11) PLEASE NOTE AN ELECTRICAL PLAN AND SUB-PERMIT WILL |
| | BE REQUIRED FOR POWER SUPPLY TO THE DISHWASHER AND |
| | RELOCATION OF THE WATER HEATER (IF APPLICABLE TO THE |
| | PROJECT)- SECS. 105.1 & 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |