Plan Review Notes
Plan Review Notes For Permit 22080638
Permit Number 22080638
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-24 10:53:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080638
 ADD: 255 EVERNIA ST. # 1518
 CONT: DESIGN CONCEPTS REMODELING
 TEL: 954-543-1327
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT. 24TH/2022
 ACTION: DENIED / VINYL FLOORING
 WE TRIED REACHING OUT TO THE CONTRACTOR AT 954-643-1327
 (FROM APP) AND FROM OUR RECORDS 954-970-7338 WHICH
 TURNED OUT TO BE A FAX.
 1) THE SUBMITTED DOCUMENTS DIVERSIFIED INDUSTRIES SOUND
 TRANSMISSION 6-INCH CONCRETE SLAB WITH SUSPENDED
 CEILING-GYPSUM BOARD WITH 3 ?? INCH FIBERGLASS
 INSULATION OVERLAID WITH DURALUX FLOOR AND FLOOR
 MUFFLER UNDERLAYMENT. AGAIN, WE DO NOT EXCEPT TEST
 REPORTS WITH DROPPED CEILINGS, ONLY 6 INCH SLABS. THE
 ONLY EXCEPTION ARE BUILDINGS THAT THE BUILDING
 DEPARTMENT HAS PROOF OF 8-INCH CONCRETE SLABS NO
 DROPPED CEILINGS.
 THE STRAND AT 255 EVERNIA DOES HAVE 8-INCH CONCRETE
 SLABS. ORIGINAL BUILD. PERMIT 99121621. THIS BUILDING
 WE WILL ACCEPT 8-INCH CONCRETE SLABS NO DROPPED
 CEILINGS. WE NEED TO SEE ALL 3 TEST REPORTS FOR STC,
 IIC AND FLAME SPREAD OR FOR VINYL LVT/ LPT WITHIN
 TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 PILL TEST
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. LVT & LPT
 LUXURY VINYL TILE. FLOOR FINISH CLASSIFICATION AS
 REQUIRED IN SECTION 804.2 CLASSIFICATION AND 804.3
 TESTING AND IDENTIFICATION OF THE 2020 FBC-B. 804.2 &
 804.3/ ASTM E648 OR NFPA 253
  
 1ST ROUND OF COMMENTS. THE CONTRACTOR SUBMITTED SPECS
 FOR FLOOR MUFFLER ULTRASEAL FLOOR UNDERLAYMENT 2MM. THE
 CITY IS IN RECEIPT OF THE FLAME SPREAD REPORT. WE HAVE
 A TEST REPORT FOR THE STC= 73DB BUT IT IS FOR A 6-INCH
 CONCRETE SLAB WITH DROPPEDDRYWALL GRID CEILING
 CONSISTING OF 5/8 INCH TYPE X GYPSUM BOARD, 12 INCH
 PLENUM WITH 3 ?? INCH FIBERGLASS INSULATION.
  
 2ND REQUEST. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP),
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C)2ND REQUEST. FBC-B 804.4.4.1 SOFT FLOOR FINISHES
 (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING)
 WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS
 SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 PILL
 TEST (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. LVT &
 LPT LUXURY VINYL TILE. FLOOR FINISH CLASSIFICATION AS
 REQUIRED IN SECTION 804.2 CLASSIFICATION AND 804.3
 TESTING AND IDENTIFICATION OF THE 2020 FBC-B. 804.2 &
 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  