| Plan Review Notes For Permit 22080597 |
| Permit Number |
22080597 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-22 11:04:57 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - IS THERE TO ALSO BE A DRYER ADDED WITH THIS WASHING | | | MACHINE? IF SO PROVIDE A DRAWING INDICATING THE DRYER | | | DUCT SIZE AND TERMINATION LOCATION. FRC M1502 | | | | | | 2 - NEED EXHAUST FOR WATER CLOSET COMPARTMENT OR WINDOW | | | OF NOT LESS THAN 3 SQ FEET FBC RESIDENTIAL | | | | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|