| 2023-04-04 14:23:42 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - THE DESCRIPTION SAYS |
| | "EXPAND DOWNSTAIRS BATHROOM", HOWEVER, YOUR PLANS DO |
| | NOT SHOW AN EXISTING VERSUS PROPOSED PLAN THAT WOULD |
| | ALLOW US TO DO A PROPER REVIEW. PLEASE PROVIDE AN |
| | EXISTING AND PROPOSED FLOOR PLAN THAT SHOWS THE CHANGES |
| | FROM THE OLD TO THE NEW. |
| | |
| | 2. 2017 WPB AMEND 107.3.5.3 (12) - THE PLUMBING |
| | DRAWINGS ARE TO BE IN ISOMETRIC (RISER) FORM. THESE |
| | DRAWING DO NOT INDICATE A REVIEWABLE SET OF DRAWINGS. |
| | PLEASE SHOW A RISER THAT HAS CODE COMPLIANT VENTING AND |
| | DRAINS. SHOW PIPE SIZES WHERE NEEDED. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - THE TITLE OF PAGE 2 SAYS |
| | "PLUMBING FOR WASHER" BUT DOES NOT REPRESENT A WASHER. |
| | IT REPRESENTS A SINK. PLEASE SUBMIT THE PROPER DRAWING |
| | FOR THE APPLICATION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |