| 2022-11-21 13:18:25 | 2ND REVIEW FMC | | | PERMIT: 22080594 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1 IS FOR THE MAIN HOUSE REMODEL ONLY, THE | | | GARAGE MECHANICAL DRAWING WAS NOT SUBMITTED WITH THIS | | | NEW SUBMITTAL. PROVIDE THE MECHANICAL DESIGN INCLUDING | | | CLEARLY LABELING THE ENERGY AND MECHANICAL CALCULATIONS | | | AS TO WHICH BUILDING THEY ADDRESS. PROVIDE A SCOPE OF | | | WORK AS TO WHAT IS EXISTING AND NOT IN THE SCOPE OF | | | WORK AND EXACTLY WHAT IS IN THE SCOPE OF WORK. CASE IN | | | POINT, THE MASTER BEDROOM AREA DOES NOT SHOW ANY | | | CONDITIONING BUT THERE ARE 2 BATH EXHAUST FANS. FBC | | | 107.3.5 | | | | | | 2) THE ARCHITECT KEITH D CHAMBERS MUST DIGITALLY SIGN | | | THE MECHANICAL DRAWINGS. F.S. 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|