| 2022-09-08 11:12:13 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE CLARIFY THE CONFLICTING INSTANCE OF THE AIR |
| | CONDITIONING IN THE MAIN HOUSE. WILL THIS BE AN AIR |
| | HANDLER ON THE FIRST FLOOR, SECOND FLOOR OR A ROOF TOP |
| | UNIT? WILL THERE BE A SEPARATE CONDENSER, IF SO, PLEASE |
| | LOCATE ON ELECTRICAL PLAN? PLEASE DETAIL ALL UNITS ON |
| | ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS. |
| | FBC 107.2 AND NEC 215.5 |
| | 2) PLEASE DETAIL ALL MINISPLIT AND THEIR ASSOCIATED |
| | OUTDOOR UNIT LOCATIONS ON ELECTRICAL PLANS. IN ADDITION |
| | PLEASE PROVIDE THERE SPECIFICATIONS, IE, VOLTAGE AMPS |
| | AND WHETHER THE ASSOCIATED UNITS ARE POWER FROM THE |
| | MAIN UNIT. |
| | 3) PLEASE CLARIFY THE WATER HEATER LOCATIONS AND |
| | SPECIFICATIONS. THERE IS ONLY ONE INSTANCE ON A PANEL |
| | SCHEDULE INDICATING A WATER HEATER. PLEASE DETAIL ALL |
| | UNITS ON ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD |
| | CALCULATIONS. FBC 107.2 AND NEC 215.5 |
| | 4) PLEASE DETAIL POOL EQUIPMENT LOCATIONS ON ELECTRIC |
| | PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS. FBC 107.2 |
| | AND NEC 215.5 |
| | 5) PLEASE CORRECT MISLABELED PANEL SCHEDULES. FBC 107.2 |
| | 6) PLEASE PROVIDE ACCURATE ELECTRICAL RISER DIAGRAM |
| | DETAILING ALL ELECTRIC PANELS, DISCONNECTS, METERS, |
| | CONDUIT AND CONDUCTOR SIZES, OVERCURRENT PROTECTION AND |
| | GROUNDING ELECTRODE SYSTEMS AS APPLICABLE. NEC 215.5, |
| | NEC 250.30 AND 250.32 FOR GES REQUIREMENTS AT SEPARATE |
| | STRUCTURES |
| | 7) PLEASE DETAIL ELECTRIC FEEDER AND SERVICE LOAD |
| | CALCULATIONS FOR MAIN ELECTRIC SERVICE AND ALL |
| | APPLICABLE PANELS WITH ACCURATE LABELS FOR EACH. ENSURE |
| | TO INCLUDE ALL APPLICABLE LOADS AS PER NEC 220 PART III |
| | OR PART IV FOR OPTIONAL CALCULATIONS IN EACH |
| | CALCULATION. FBC 107.2 AND NEC 215.5 |
| | 8) PLEASE DETAIL OUTSIDE RECEPTACLES AS REQUIRED BY NEC |
| | 210.52(E) AND NEC 210.63 |
| | 9) PLEASE CLARIFY CONFLICTING LOCATIONS FOR |
| | REFRIGERATOR AND RANGE IN MAIN HOUSE. IT IS DIFFERENT |
| | ON FLOOR PLANS, ELECTRIC PLANS AND OTHERS. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |