Plan Review Notes
Plan Review Notes For Permit 22080594
Permit Number 22080594
Review Stop E
Sequence Number 1
Notes
Date Text
2022-09-08 11:12:13ELECTRIC REVIEW FAILED
 1) PLEASE CLARIFY THE CONFLICTING INSTANCE OF THE AIR
 CONDITIONING IN THE MAIN HOUSE. WILL THIS BE AN AIR
 HANDLER ON THE FIRST FLOOR, SECOND FLOOR OR A ROOF TOP
 UNIT? WILL THERE BE A SEPARATE CONDENSER, IF SO, PLEASE
 LOCATE ON ELECTRICAL PLAN? PLEASE DETAIL ALL UNITS ON
 ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS.
 FBC 107.2 AND NEC 215.5
 2) PLEASE DETAIL ALL MINISPLIT AND THEIR ASSOCIATED
 OUTDOOR UNIT LOCATIONS ON ELECTRICAL PLANS. IN ADDITION
 PLEASE PROVIDE THERE SPECIFICATIONS, IE, VOLTAGE AMPS
 AND WHETHER THE ASSOCIATED UNITS ARE POWER FROM THE
 MAIN UNIT.
 3) PLEASE CLARIFY THE WATER HEATER LOCATIONS AND
 SPECIFICATIONS. THERE IS ONLY ONE INSTANCE ON A PANEL
 SCHEDULE INDICATING A WATER HEATER. PLEASE DETAIL ALL
 UNITS ON ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD
 CALCULATIONS. FBC 107.2 AND NEC 215.5
 4) PLEASE DETAIL POOL EQUIPMENT LOCATIONS ON ELECTRIC
 PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS. FBC 107.2
 AND NEC 215.5
 5) PLEASE CORRECT MISLABELED PANEL SCHEDULES. FBC 107.2
 6) PLEASE PROVIDE ACCURATE ELECTRICAL RISER DIAGRAM
 DETAILING ALL ELECTRIC PANELS, DISCONNECTS, METERS,
 CONDUIT AND CONDUCTOR SIZES, OVERCURRENT PROTECTION AND
 GROUNDING ELECTRODE SYSTEMS AS APPLICABLE. NEC 215.5,
 NEC 250.30 AND 250.32 FOR GES REQUIREMENTS AT SEPARATE
 STRUCTURES
 7) PLEASE DETAIL ELECTRIC FEEDER AND SERVICE LOAD
 CALCULATIONS FOR MAIN ELECTRIC SERVICE AND ALL
 APPLICABLE PANELS WITH ACCURATE LABELS FOR EACH. ENSURE
 TO INCLUDE ALL APPLICABLE LOADS AS PER NEC 220 PART III
 OR PART IV FOR OPTIONAL CALCULATIONS IN EACH
 CALCULATION. FBC 107.2 AND NEC 215.5
 8) PLEASE DETAIL OUTSIDE RECEPTACLES AS REQUIRED BY NEC
 210.52(E) AND NEC 210.63
 9) PLEASE CLARIFY CONFLICTING LOCATIONS FOR
 REFRIGERATOR AND RANGE IN MAIN HOUSE. IT IS DIFFERENT
 ON FLOOR PLANS, ELECTRIC PLANS AND OTHERS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER