2023-02-24 12:27:122ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22080569
 2/24/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1, 2, & 4
 FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES
  
 1) 2ND REVIEW- SHEET P.219: IN RESPONSE TO MY 1ST
 REVIEW COMMENTS THE MEP NARRATIVE IS DIRECTING ME TO
 PLAN REVISIONS SUBMITTED UNDER PERMIT 22120277 WHICH
 CURRENTLY HAS A FAILED 1ST PLUMBING REVIEW FOR
 INCOMPLETE PLANS. COMMENTS FROM THE REVIEW INDICATE
 MISSING PLAN SHEETS P106A, 106A, P106B, P106C, P107A,
 P107B, & P107C. I RESEARCHED THE PLANS AND NARRATIVE
 UNDER 22120277 AND THE MISSING SHEETS ARE THE NEW 8TH
 FLOOR KITCHEN AND BAR WASTE AND WATER PIPING PLANS AS
 CALLED OUT IN THE 22120277 NARRATIVE. I WAS ABLE TO
 LOCATE THE KITCHEN AND BAR PLUMBING LAYOUT DRAWINGS AND
 ISOMETRICS FOR THE RELOCATED KITCHEN SHOWN ON SHEETS
 P.517 & P.714 AND HAVE THESE COMMENTS- A, B, & C.
  
 A) THE KW DRAIN LINES SHOWN ON SHEETS P.517 & P.714 ARE
 GREASE WASTE (GW)? IF THAT IS CORRECT IT APPEARS THE
 HANDSINKS AND FLOOR SINKS UNDER ICE MAKERS AND ICE BINS
 ARE DRAINING INTO THE GREASE WASTE INTERCEPTOR WHICH IS
 NOT ALLOWED PER SEC. 1003.3.1 FBC P. PLEASE REVISE THE
 DRAWINGS TO INDICATE DRAINAGE FROM THESE FIXTURES
 DISCHARGING TO THE SANITARY SYSTEM.
  
 B) PLEASE PROVIDE A COMPLETE GREASE WASTE RISER DRAWING
 THAT INCLUDES THE GW PIPE FROM THE 8TH FLOOR INTO THE
 INTERCEPTOR AND THE OUTLET PIPE POINT OF CONNECTION TO
 THE SANITARY. PLEASE INCLUDE CLEANOUT LOCATIONS. THE
 CURRENT PLANS DO NOT SHOW THE PIPE CONTINUATION THROUGH
 THE FLOORS TO THE INTERCEPTOR LOCATION- SEC. 1003.3.1.
  
 C) PLEASE PROVIDE GREASE WASTE CALCULATIONS AND AN
 EQUIPMENT SCHEDULE FOR THE INTERCEPTOR- SEC. 1003.3.5.
  
 2) 2ND REVIEW- SHEET P.219: THE RESPONSE NARRATIVE
 PROVIDES A LAUNDRY LIST OF CHANGES THAT INCLUDE MANY
 ITEMS NOT RELATED TO THE PLUMBING PLANS SUCH AS TENNIS
 COURT DOORS, EXTERIOR TERRACE MODIFICATIONS AND
 LIGHTING ETC. I WAS ABLE TO RESEARCH AND FIND SOME OF
 THE REQUIRED PLUMBING DRAWINGS FOR THE RELOCATED 8TH
 FLOOR BATHS AND THE HOTEL ROOM MODIFICATIONS, HOWEVER I
 WAS NOT ABLE TO LOCATE REVISED RISER DRAWINGS FOR THE
 RELOCATED POOL EQUIPMENT ROOM SHOWN ON SHEETS P.107A &
 P.509. PLEASE NOTE THAT POOL WASTE WATER SHALL NOT
 DRAIN INTO THE SANITARY AND THERE ARE SEVERAL FLOOR
 DRAINS IN PROXIMITY OF EQUIPMENT. POOL WASTE WATER
 SHALL BE DECHLORINATED AND DRAIN TO THE STORM SYSTEM IN
 ACCORDANCE WITH SEC. 90-205(1) WPB CODE OF ORDINANCES.
 PLEASE PROVIDE THE REQUIRED DRAWINGS AND DETAILS
 SHOWING CODE COMPLIANT DISPOSAL.
  
 4) 2ND REVIEW- SHEETS P.219, P.220, P.221, P.222,
 P.223, P.224: PROVIDE REVISED ENLARGED AND DETAILED
 ARCHITECTURAL DRAWINGS FOR THE ACCESSIBLE BATHROOMS-
 SEC. 213.2 & SECS. 603.1- 610.1 FBC ACC. THE NARRATIVE
 REFERS TO SHEETS A0.202 & A0.203 WHICH WERE NOT
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  