Plan Review Notes
Plan Review Notes For Permit 22080569
Permit Number 22080569
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-31 10:27:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080569
 8/30/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.219: THE SUBMITTED NARRATIVE OF PLUMBING
 CHANGES PROVIDES VERY GENERAL INFORMATION. PLEASE
 PROVIDE A DETAILED NARRATIVE THAT ITEMIZES ALL
 REVISIONS MADE TO THE PLAN FROM REV-2 (12/14/2020) TO
 REV-11 (08/05/2020). PLEASE UPDATE THE REVISION
 SCHEDULE ON THE PLAN WITH DELTA SYMBOLS AND DATES THAT
 CORRESPOND WITH THE DESIGN CHANGES- SEC. 107.2.1 WPB.
 COMPARISONS OF THE APPROVED PLAN (09/15/2021) AND THE
 SUBMITTED REVISED PLANS SHOW CHANGES THAT INCLUDE:
 A) REMOVAL OF THE MEN'S AND WOMEN'S GANG BATHROOMS,
 POOL EQUIPMENT ROOM, & SERVICE BAR.
 B) MULTIPLE CHANGES TO BATHROOM LAYOUTS AND PLUMBING
 FIXTURES IN THE ROOMS INCLUDING A NEW ADA COMPLIANT
 ROOM 1.3.
 C) A NEW KITCHEN WHICH WILL REQUIRE A GREASE
 INTERCEPTOR AND A GREASE WASTE LINE- SEC. 1003.3.1 FBC
 P.
 PLEASE REVISE ALL PLUMBING AND ARCHITECTURAL PLANS THAT
 ARE AFFECTED BY THE CHANGES IN DESIGN.
  
 2) P.219: SUBMIT REVISED SHEET P.509 WHICH IS CALLED
 OUT IN THE NOTE AT THE KITCHEN- SEC. 107.2.1 WPB.
  
 3) P.219, P.220, P.221, P.222, P.223, P.224: CHANGES TO
 ACCESSIBLE BATHROOM FIXTURE LAYOUTS, PLUMBING PIPING
 LAYOUTS AND RISERS ARE INDICATED. PLEASE SUBMIT THE
 REVISED SHEETS CALLED OUT ON THE PLANS- P.701A, &
 P.703- SEC. 107.2.1 WPB. ALTERNATIVELY, IF NEW SHEETS
 HAVE BEEN PROVIDED PLEASE REVISE THE TARGET NOTES TO
 MATCH.
  
 4) P.219, P.220, P.221, P.222, P.223, P.224: PROVIDE
 REVISED ENLARGED AND DETAILED ARCHITECTURAL DRAWINGS
 FOR THE ACCESSIBLE BATHROOMS- SEC. 213.2 & SECS. 603.1-
 610.1 FBC ACC.
  
 5) P.219: REFERENCE NOTE FOR ENLARGED UNIT PIPING
 LAYOUT NOT PROVIDED IN ADA ROOM 1.3A- SEC. 107.2.1 WPB.
  
 6) P.220: REFERENCE NOTES FOR ENLARGED UNIT PIPING
 LAYOUT NOT PROVIDED IN SUITE 4KL, AND ROOM 1.3A- SEC.
 107.2.1 WPB.
  
 7) P.221 & P.222: REFERENCE NOTES FOR ENLARGED UNIT
 PIPING LAYOUT NOT PROVIDED IN MANY OF THE ROOMS. PLEASE
 REVIEW AND REVISE- SEC. 107.2.1 WPB.
  
 8) P.501 & P.503A: PLEASE SUBMIT THE REVISED SHEETS
 CALLED OUT ON THE PLANS- P.701A, & P.703- SEC. 107.2.1
 WPB. ALTERNATIVELY, IF NEW SHEETS HAVE BEEN PROVIDED,
 PLEASE REVISE THE TARGET NOTES TO MATCH.
  
 9) P.512: THE NARRATIVE INDICATES NEW BATHROOMS AT THE
 12TH FLOOR. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 BASED ON THE TABLE.
  
 10) P.512: THE NARRATIVE DOES NOT PROVIDE ANY
 INFORMATION ABOUT THE NEW LOCKER ROOM BATHS- SEC.
 107.2.1 WPB. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 BASED ON THE TABLE.
  
 11) P.512: PROVIDE REVISED THE MAIN SANITARY RISER
 DRAWINGS AND DFU CALCULARTIONS BASED ON THE ADDED
 PLUMBING FIXTURES IN THE TOWER- SEC. 107.3.5.1.3 WPB,
 AND SEC. 710.1 FBC P.
  
 12) P.512: PROVIDE REVISED ENLARGED AND DETAILED
 ARCHITECTURAL DRAWINGS FOR THE ACCESSIBLE BATHROOMS ON
 THE 7TH AND 12TH FLOORS SEC. 213.2 & SECS. 603.1- 610.1
 FBC ACC.
  
 13) P.512: SHOW THE SOURCES OF THE HOT WATER AND
 CLARIFY IF NEW WATER HEATERS HAVE BEEN SELECTED AS PART
 OF THE REVISION TO SUPPLY THE FIXTURES- SEC. 607.1 FBC
 P. PLEASE PROVIDE WATER HEATER EQUIPMENT SCHEDULES IF
 APPLICABLE- SEC. 107.2.1 WPB.
  
 14) P.512: THE 1/2-INCH FIXTURE SUPPLY PIPES SUPPLYING
 HOT WATER TO THE LAVATORIES HAVE EXCEEDED THE MAXIMUM 2
 FT. LENGTHS ALLOWABLE PER TABLE C404.5.1 FBC EC. THE
 HWR LINE MUST LOOP DOWN TO THE LAVS, OR POINT OF USE
 WATER HEATERS SHALL BE PROVIDED.
  
 15) P.512: INDICATE HOW TRAP SEAL PROTECTION IS BEING
 PROVIDED FOR THE FLOOR DRAINS- SEC. 1002.4.1 FBC P.
  
 16) P.705A: BT-X & SH-X SHOWN IN THE RISER FOR UNITS
 1.3A- 4.2A NEED TO BE VENTED PER SEC. 901.2.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  