| 2022-09-27 17:18:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22080521 |
| | ADD: 1501 BELVEDERE RD 1ST FLOOR COMMON AREAS |
| | CONT: VREDEX CONSRUCTION |
| | TEL: 561-440-1600 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. SEPT. 27TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2)COMPLIED. SHEET A0.4 THE FLOOR PLAN THE LIFE SAFETY |
| | PLAN SHOWS THE EAST INTERIOR EXIT STAIRWAYS CONTINUING |
| | TO THE EXIT BY A 2-HOUR FIRE RATED EXIT PASSEAGE WAY |
| | WITH 90- MINUTE OPENING PROTECTIVES. |
| | |
| | 2A-B) COMPLIED. |
| | |
| | 2C) 2ND REQUEST. PLEASE REVIEW SHEET M1.2 FOR ALL |
| | DUCTWORK AND RELATED MECHANICAL EQUIPMENT THAT IS |
| | LOCATED IN THE CEILINGS OF BOTH THE EAST EXIT |
| | PASSAGEWAY. PLEASE REVIEW SECTION 1024.6 PENETRATIONS |
| | INTO OR THROUGH EXIT PASSAGEWAYS, PROHIBITED, PLUMBING, |
| | MECHANICAL EQUIPMENT, AND ELECTRICAL PIPING AND |
| | DEVICES. 2020 FBC-BUILDING. THE RESPONSE THE ENGINEER |
| | HAS ADDED A 2- HOUR SHAFT WALL CEILING DETAIL TO |
| | CONCEAL THE DUCTWORK. SHAFTWALL ARE BUILT FLOOR TO |
| | CEILING, THEY ARE TO BE BUILT WITH STRUCTURAL METAL |
| | STUDS, U415 IS FOR NONBEARING WALL RATING. WHILE NOT |
| | TESTED BY UL, THE SYSTEM HAS BEEN TESTED FOR FIRE AND |
| | IS COVERED FOR USE THROUGHOUT THE UNITED STATES. THE |
| | FIRE TEST NUMBER IS WHI 495-PSH-0154/0167 AND REPORT |
| | NUMBER IS AER-09038 AVAILABLE AT WWW.P-E-I.COM.ALSO SEE |
| | CAVITY SHAFTWALL SYSTEMS, TECHNICAL DATA FOR MAXIMUM |
| | HORIZONTAL SPANS FOR I-STUD ASSEMBLIES 2 HR. FIRE |
| | RESTRICTIVE RATING, HORIZONTAL SHAFTWALL DUCT AND |
| | CEILING ASSEMBLIES 09 21 16.23/NGC BUYLINE1100. PROVIDE |
| | A SHAFTWALL ASSEMBLY THAT HAS A 2 HOUR FIRE RATING |
| | WHERE IT HAS BEEN TESTED HORIZONTALLY. |
| | |
| | 2D-E) COMPLIED. |
| | |
| | 3)COMPLIED. |
| | |
| | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |