| Plan Review Notes For Permit 22080480 |
| Permit Number |
22080480 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-14 08:24:25 | 2ND REVIEW FMC | | | PERMIT: 22080480 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ATTACHED DRAWINGS ARE NOT READABLE PLEASE SUBMIT | | | EACH ORIGINAL ON A SEPARATE PAGE AS THE ONES SUBMITTED | | | ARE COPIES AND ARE NOT CLEAR, CANNOT READ THE WORDS. A | | | COMPLETE SET OF DRAWINGS WERE NOT SUBMITTED AS I DO NOT | | | SEE THE MAKE UP AIR CALCULATIONS. SHEET 2 OF 3 | | | INDICATES 4 DIFFERENT COMPANIES THAT MANUFACTURE | | | DUCTWORK FOR THE ROASTERS WITH AN AFTERBURNER. NORDFAB | | | IS NOT ON THAT LIST. PLEASE PROVIDE THE SPECIFICATIONS | | | FROM THE ONE THAT WILL BE USED IN THIS DESIGN. THE | | | DUCTWORK DETAILS ON SHEETS M-3 AND SHEET 2 OF 2 DO NOT | | | MATCH. THE INSTALLATIONS OF EACH ROASTER AND THE | | | AFTERBURNER MUST BE SUBMITTED, SHEET M-1 IS NOT | | | READABLE. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|