| 2022-08-16 10:29:47 | 1ST REVIEW FMC |
| | PERMIT: 22080480 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS SUBMITTAL IS INCOMPLETE SO I CANNOT DO A |
| | REVIEW. THE INFORMATION SUBMITTED IS COPIES OF THE |
| | DOCUMENTS AND ARE NOT CLEAR. PLEASE PROVIDE THE |
| | INSTALLATION INSTRUCTIONS FOR EACH ROASTER AND THE |
| | NORDFAB DUCTWORK. FBC 107.3.5 |
| | |
| | 2) PLEASE PROVIDE A BUILDING PERMIT APPLICATION AND |
| | ARCHITECTURAL DRAWINGS FOR THE INSTALLATION OF THESE |
| | ROASTERS AND THE PENETRATIONS OF THE ROOF IN THIS |
| | WAREHOUSE. PROVIDE THE OCCUPANCY CLASSIFICATION THAT |
| | THIS BUILDING WILL BE RECLASSIFIED TO WITH THIS |
| | INSTALLATION. FBC 107.3.5 |
| | |
| | 3) WHAT IS THE FUEL SOURCE FOR THESE ROASTERS? IF THEY |
| | ARE GAS FIRED THEN A FUEL GAS PERMIT WOULD BE REQUIRED. |
| | |
| | 4) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THE |
| | INSTALLATION OF THESE ROASTERS INCLUDING THE REQUIRED |
| | COMBUSTION AND MAKEUP AIR. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |