| 2022-10-21 08:02:56 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - ALL |
| | HOT/TEMPERED WATER MUST BE LIMITED BY A MIXING DEVICE. |
| | THE THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE |
| | THE LIMITING DEVICE FOR HOT/TEMPERED WATER DELIVERY. |
| | PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE |
| | PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN |
| | ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER |
| | SUPPLIED FOR PUBLIC HANDWASHING 607.1.2/419.5. ALSO, |
| | THE DEVICE SHALL MEET THE ASSE 1017 STANDARD AND BE |
| | INSTALLED AT THE HOT WATER SOURCE PER 613.1. PLEASE |
| | INCLUDE DETAILS THAT SHOW A MIXING VALVE ABOVE THE |
| | WATER HEATER THAT REGULATES ALL HOT/TEMPERED WATER. |
| | |
| | 2. 2020 FPC 905.4 - PAGE P701 DETAIL #14 - EVEN THOUGH |
| | THIS DETAIL IS NOT USED, PLEASE REMOVE AS IT IS NOT TO |
| | CODE. DRY VENTS ARE NOT ALLOWED TO BE HORIZONTAL UNTIL |
| | AT LEAST 6 INCHES ABOVE THE FLOOD RIM OF THE FIXTURE |
| | SERVED. THE ONLY EXCEPTION TO THAT IS VENTS REQUIRED |
| | FOR EXTERIOR GREASE TRAPS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |