2022-10-21 08:02:561ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - ALL
 HOT/TEMPERED WATER MUST BE LIMITED BY A MIXING DEVICE.
 THE THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE
 THE LIMITING DEVICE FOR HOT/TEMPERED WATER DELIVERY.
 PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE
 PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER
 SUPPLIED FOR PUBLIC HANDWASHING 607.1.2/419.5. ALSO,
 THE DEVICE SHALL MEET THE ASSE 1017 STANDARD AND BE
 INSTALLED AT THE HOT WATER SOURCE PER 613.1. PLEASE
 INCLUDE DETAILS THAT SHOW A MIXING VALVE ABOVE THE
 WATER HEATER THAT REGULATES ALL HOT/TEMPERED WATER.
  
 2. 2020 FPC 905.4 - PAGE P701 DETAIL #14 - EVEN THOUGH
 THIS DETAIL IS NOT USED, PLEASE REMOVE AS IT IS NOT TO
 CODE. DRY VENTS ARE NOT ALLOWED TO BE HORIZONTAL UNTIL
 AT LEAST 6 INCHES ABOVE THE FLOOD RIM OF THE FIXTURE
 SERVED. THE ONLY EXCEPTION TO THAT IS VENTS REQUIRED
 FOR EXTERIOR GREASE TRAPS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved