Plan Review Notes
Plan Review Notes For Permit 22080397
Permit Number 22080397
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-09-14 13:48:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF "DEMO EXISTING FLLOR AND
 ADD NEW ONE", HOWEVER, THERE IS NO INDICATION OF A SPEC
 SHEET NOR A PRODUCT NAME FOR THE ACTUAL PROPOSED
 FLOORING.
  
 FINISHED FLOORING CAN BE MANUFACTURED AROUND THE WORLD
 AND NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FINISHED FLOORING COULD HAVE DIFFERENT MEANINGS AND IF
 NOT CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC.
  
 PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE,
 TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A SPEC SHEET
 NOR A FIRE BEHAVIOR RATING.
  
 FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL, VINYL
 PLANKS, LUXURY VINYL PLANKS, LAMINTE, CORK, WOOD PLEASE
 PROVIDE THE MANUFACTURE PRODUCT FLAME SPREAD/PRODUCT
 SAFETY TEST SHEET
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FINSIHED
 FLOORING TYPE AND/OR NAME AND THE PRODUCT SPEC SHEETS
 OF THE PROPOSED FINISHED
 FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE IS AN INDICATION OF "NO FIRE SPRINKLER WORK"
 HOEVER, THERE ARE INDICATIONS OF WALLS BEING REMOVED
 AND RECONSTRUCTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 SHOULD FIRE SPRINKLER MODIFICATION NOT BE REQUIRED A
 LETTER FROM THE CONTRACTOR SHALL BE PROVIDED TO THE
 FIRE INSPECTION ON INSPECTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT
  
  
 3) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND
 RECONSTRUCTION PERIODS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND FIR ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED FIRE SPRINKLER AND FIRE ALARM CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  