| 2022-09-14 13:48:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF "DEMO EXISTING FLLOR AND |
| | ADD NEW ONE", HOWEVER, THERE IS NO INDICATION OF A SPEC |
| | SHEET NOR A PRODUCT NAME FOR THE ACTUAL PROPOSED |
| | FLOORING. |
| | |
| | FINISHED FLOORING CAN BE MANUFACTURED AROUND THE WORLD |
| | AND NOT ALL ARE TESTED AND MEETING LISTED AND NFPA |
| | STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FINISHED FLOORING COULD HAVE DIFFERENT MEANINGS AND IF |
| | NOT CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE |
| | VINYL/LAMINATE ETC. |
| | |
| | PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE, |
| | TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A SPEC SHEET |
| | NOR A FIRE BEHAVIOR RATING. |
| | |
| | FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL, VINYL |
| | PLANKS, LUXURY VINYL PLANKS, LAMINTE, CORK, WOOD PLEASE |
| | PROVIDE THE MANUFACTURE PRODUCT FLAME SPREAD/PRODUCT |
| | SAFETY TEST SHEET |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FINSIHED |
| | FLOORING TYPE AND/OR NAME AND THE PRODUCT SPEC SHEETS |
| | OF THE PROPOSED FINISHED |
| | FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | |
| | 2) THERE IS AN INDICATION OF "NO FIRE SPRINKLER WORK" |
| | HOEVER, THERE ARE INDICATIONS OF WALLS BEING REMOVED |
| | AND RECONSTRUCTION. |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL |
| | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE |
| | AND COMPLIANCE BY CERTIFIED CONTRACTORS. |
| | |
| | SHOULD FIRE SPRINKLER MODIFICATION NOT BE REQUIRED A |
| | LETTER FROM THE CONTRACTOR SHALL BE PROVIDED TO THE |
| | FIRE INSPECTION ON INSPECTION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT |
| | |
| | |
| | 3) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE |
| | MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND |
| | RECONSTRUCTION PERIODS. |
| | |
| | ANY AND ALL WORK ON THE FIRE SPRINKLER AND FIR ALARM |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED FIRE SPRINKLER AND FIRE ALARM CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |