Plan Review Notes
Plan Review Notes For Permit 22080397
Permit Number 22080397
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-06 10:00:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE SEVERAL MISTAKES ON SHEET IF. PLEASE
 CORRECT.
 A) THERE ARE A COUPLE OF REFERENCES TO THE 2020 FRBC.
 NOT SURE WHAT CODE THIS IS. THE RESIDENTIAL CODE DOES
 NOT APPLY TO CONDOMINIUMS. THE 2020 FBC EXISTING
 BUILDING AND 2020 FBC BUILDING ARE THE CODES THAT APPLY
 TO THIS PROJECT. FBC 107.2.1
 B) THE LIFE SAFETY NOTES SPECIFY TYPEV CONSTRUCTION.
 THIS IS A HIGH RISE BUILDING AND WOULD BE A MINIMUM OF
 TYPE II CONSTRUCTION. FBC CHAPTER 5
 C) THE TYPE OF OCCUPANCY FOR THIS BUILDING IS R-2. FBC
 310
  
 2) THERE ARE SEVERAL MISTAKES ON SHEET A-005. PLEASE
 CORRECT.
 A) UNDER STRUCTURAL NOTES THE ULTIMATE WIND SPEED IS
 170 MPH AND THE NOMINAL WIND SPEED IS 132 MPH. FBC
 1609.3
 B) THIS BUILDING IS NOT ALLOWED TO HAVE STRUCTURAL
 TIMBERS. FBC 601
 C) THE TYPICAL SUSPENDED CEILING DETAIL DOESN'T APPLY
 SINCE THERE ARE NO TIMBER TRUSSES IN THIS BUILDING. FBC
 601
  
 3) SUBMIT THE FOLLOWING INFORMATION FOR THE NEW
 FLOORING.
 A) TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE,
 LAMINATE, WOOD, MARBLE, ETC.).
 B) DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS
 OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED
 CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
 C) PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT.
 D) TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 E) TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 - SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 - FBC 603.1 FLAME SPREAD AND SMOKE DEVELOPED - ASTM E
 84-09
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 - WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 -
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4) THE VALUE FOR THIS PROJECT APPEARS TO BE TOO LOW FOR
 THE PROPOSED WORK. SUBMIT AN ITEMIZED COST BREAKDOWN.
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  