Plan Review Notes
Plan Review Notes For Permit 22080363
Permit Number 22080363
Review Stop B
Sequence Number 2
Notes
Date Text
2022-11-14 09:28:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080363
 ADD: 330 CLEMATIS ST. # 116
 CONT: BLUE WATER VENTURES OF PALM BEACH
 TEL: 561-339-6128
 E-MAIL:
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 14TH/2022
 ACTION: DENIED
  
 1A-G) COMPLIED, EXISTING STAIRS.
  
 1H) 2ND REQUEST. PLEASE NOTE MISSING DIMENSION BETWEEN
 THE 4-FOOT DIMENSION AND TWO FOOT TEN INCHES SHOWN FOR
 COUNTER HEIGHT. PLEASE NOTE THE REACH RANGES FOR FRONT
 AND SIDE APPROACH WITH OBSTRUCTED VIEW ARE DIFFERENT
 OBSTRUCTED FRONT APPROACH IS 44 INCHES WHEN THERE IS NO
 OBSTRUCTION BELOW THE COUNTERTOP. IT APPEARS TO HAVE A
 DISHWASHER THERE SEE FIGURE 308.2.2 OF THE ACCESS
 .CODE. SIDE APPROACH REVIEW FIGURE 308.2.2 46 INCHES
 FOR AN OBSTRUCTED SIDE APPROACH. PLEASE ALSO SHOW ON
 THE FLOOR PLAN IF YOU ARE USING A FRONT APPROACH OR
 SIDE APPROACH. REACH RANGES NEEDS TO INCLUDE REACHING
 THE PROGRAM PANEL FOR THE COOKING TIME NOT JUST THE
 OPENING MECHANISM!!!!!
  
 1ST ROUND COMMENTS. DETAIL A1 SHOWS THE BREAK ROOM WITH
 A MICROWAVE IN THE UPPER CABINETS. THIS CONFIGURATION
 DOES NOT COMPLY WITH 2020 FBC-ACCESSIBILITY CODE FOR:
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 1I)COMPLIED, SINK HEIGHT.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  