Plan Review Notes
Plan Review Notes For Permit 22080301
Permit Number 22080301
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-16 13:21:23THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE A FLOOR PLAN WITH IDENTIFICATION OF EXITS,
 COMMON PATH OF TRAVEL AND TRAVEL DISTANCE PER NFPA 101
 CHAPTER 7.
 2. PROVIDE EXIT MARKING AND DIRECTION PER NFPA 101
 CHAPTER 7.
 2.ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
 3.ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
 4.THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]