| Plan Review Notes For Permit 22080280 |
| Permit Number |
22080280 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-22 12:40:38 | FIRE REVIEW COMMENTS: | | | | | | THE APPLICATION INDICATES NEW FLOORING. | | | | | | THERE WERE NO SPECIFICATIONS PROVIDED ON THE TYPE OF | | | FINISHED FLOORING AND THE UNDERLAYMENT MATERIAL. | | | | | | PROVIDE SPECIFICATIONS AND THE PROPOSED FLOORING AND | | | UNDERLAYMENT OF THE MATERIALS FIRE PERFORMANCE | | | INCLUDING THE CRITICAL RADIANT FLUX OF ALL FLOORING | | | MATERIALS. NFPA 101, 10.2.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|