| 2022-09-08 15:04:42 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080265 |
| | 9/8/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A0.1: PLEASE UPDATE THE PLUMBING FIXTURE COUNT |
| | CODE REFERENCE TO INDICATE THE 2020 FBC- PLUMBING 7TH |
| | EDITION. |
| | |
| | 2) A0.1: THE PLUMBING FIXTURE COUNT NOTE REFERENCING |
| | "STORAGE A-3 ASSEMBLY" IS CONFUSING. STORAGE AND |
| | ASSEMBLY ARE SEPARATE OCCUPANCIES. THE FLOOR PLANS |
| | APPEAR TO INDICATE A MIXED OCCUPANCY OF ASSEMBLY- A3 |
| | (WORSHIP AND OTHER RELIGIOUS SERVICES) (GYMNASIUM & |
| | WORKOUT) , BUSINESS (OFFICES), AND STORAGE PER SECS. |
| | 303, 304, & 311 FBC B. TABLE 403.1 FBC P HAS SEPARATE |
| | FIXTURE REQUIREMENTS AND RATIOS FOR EACH OCCUPANCY AND |
| | USE CLASSIFICATION. MULTIPLE OCCUPANCY FIXTURE COUNTS |
| | ARE DETERMINED BY CALCULATING THE REQUIRED FIXTURE |
| | RATIOS AS SUM-TOTALS FOR EACH OCCUPANCY OR USE, AND |
| | THEN ADDING THEM TOGETHER TO GET THE TOTAL NUMBER OF |
| | FIXTURES REQUIRED. PLEASE PROVIDE A SCHEDULE THAT SHOWS |
| | THE REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE |
| | PROPOSED PROJECT AREA- SEC. 403.1.1 FBC P. |
| | |
| | 3) A0.1: PLEASE CLARIFY IF THE REMODELED RESTROOMS AND |
| | FIXTURE INSTALLATIONS WILL BE DESIGNED IN ACCORDANCE |
| | WITH THE FBC-2020 ACCESSIBILITY CODE. BASED ON THE CODE |
| | PLEASE NOTE THE FOLLOWING DEFICIENCIES ON PLAN SHEETS |
| | A3.1.3, A3.1.4, & A3.1.4. |
| | A) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE WATER |
| | CLOSETS AND LAVATORIES NOT SHOWN- SECS. 604.3 & 606.2. |
| | B) TURNING SPACE DIAMETERS NOT SHOWN- SEC. 304.3. |
| | C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | NOT SHOWN- SEC. 604.2. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS NOT SHOWN- SEC. 604.4. |
| | E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS NOT SHOWN- SEC. |
| | 606.3. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES NOT SHOWN- SEC. 603.3 |
| | G) WATER CLOSET GRAB BAR LENGTHS, EXTENSIONS, AND |
| | MOUNTING HEIGHTS NOT SHOWN- SECS. 604.5 & 609.4. |
| | H CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS NOT SHOWN- SEC. |
| | AND FIGURE 604.7. |
| | I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES NOT |
| | SHOWN- SEC. 606.2 |
| | J) CAF? SINK HEIGHT, AND CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS NOT SHOWN- SEC. 606.2. |
| | K) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE SHOWERS |
| | NOT SHOWN- SEC. 608.2.2.1 |
| | M) SHOWER GRAB BAR LENGTHS, AND MOUNTING HEIGHTS NOT |
| | SHOWN- SEC. 608.3.2. |
| | N) HEIGHT OF THE SHOWER CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SEC. 608.5.2. |
| | |
| | 4) SHEETS P301, P302, P401, P402, P701: IT APPEARS THE |
| | PLUMBING FIXTURES IN THE BATHROOMS ARE BEING REPLACED. |
| | PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING |
| | MAKES AND MODELS AND ADA CONFORMANCE APPROVAL NOTED |
| | WHERE REQUIRED- SEC. 107.2.1 WPB. |
| | |
| | 5) P302: NOTE 202 INDICATES THERE MAY BE A FOOD WASTE |
| | DISPOSER INSTALLED. PLEASE NOTE FOOD WASTE DISPOSERS |
| | SHALL NOT DISCHARGE INTO THE GREASE INTERCEPTOR- |
| | 1003.3.2 FBC P. |
| | |
| | 6) P701: A MEANS OF CONTROLLING THE HOT WATER DELIVERY |
| | TEMPERATURES AT THE NEW KITCHEN SINK AND DISHWASHER |
| | SHALL BE PROVIDED PER SEC. 607.1.1 FBC P. PLEASE NOTE |
| | THE MEANS OF CONTROL CANNOT BE THE THERMOSTAT ON THE |
| | EXISTING WATER HEATER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |