Plan Review Notes
Plan Review Notes For Permit 22080265
Permit Number 22080265
Review Stop P
Sequence Number 1
Notes
Date Text
2022-09-08 15:04:421ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080265
 9/8/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0.1: PLEASE UPDATE THE PLUMBING FIXTURE COUNT
 CODE REFERENCE TO INDICATE THE 2020 FBC- PLUMBING 7TH
 EDITION.
  
 2) A0.1: THE PLUMBING FIXTURE COUNT NOTE REFERENCING
 "STORAGE A-3 ASSEMBLY" IS CONFUSING. STORAGE AND
 ASSEMBLY ARE SEPARATE OCCUPANCIES. THE FLOOR PLANS
 APPEAR TO INDICATE A MIXED OCCUPANCY OF ASSEMBLY- A3
 (WORSHIP AND OTHER RELIGIOUS SERVICES) (GYMNASIUM &
 WORKOUT) , BUSINESS (OFFICES), AND STORAGE PER SECS.
 303, 304, & 311 FBC B. TABLE 403.1 FBC P HAS SEPARATE
 FIXTURE REQUIREMENTS AND RATIOS FOR EACH OCCUPANCY AND
 USE CLASSIFICATION. MULTIPLE OCCUPANCY FIXTURE COUNTS
 ARE DETERMINED BY CALCULATING THE REQUIRED FIXTURE
 RATIOS AS SUM-TOTALS FOR EACH OCCUPANCY OR USE, AND
 THEN ADDING THEM TOGETHER TO GET THE TOTAL NUMBER OF
 FIXTURES REQUIRED. PLEASE PROVIDE A SCHEDULE THAT SHOWS
 THE REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE
 PROPOSED PROJECT AREA- SEC. 403.1.1 FBC P.
  
 3) A0.1: PLEASE CLARIFY IF THE REMODELED RESTROOMS AND
 FIXTURE INSTALLATIONS WILL BE DESIGNED IN ACCORDANCE
 WITH THE FBC-2020 ACCESSIBILITY CODE. BASED ON THE CODE
 PLEASE NOTE THE FOLLOWING DEFICIENCIES ON PLAN SHEETS
 A3.1.3, A3.1.4, & A3.1.4.
 A) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS AND LAVATORIES NOT SHOWN- SECS. 604.3 & 606.2.
 B) TURNING SPACE DIAMETERS NOT SHOWN- SEC. 304.3.
 C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 NOT SHOWN- SEC. 604.2.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS NOT SHOWN- SEC. 604.4.
 E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS NOT SHOWN- SEC.
 606.3.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES NOT SHOWN- SEC. 603.3
 G) WATER CLOSET GRAB BAR LENGTHS, EXTENSIONS, AND
 MOUNTING HEIGHTS NOT SHOWN- SECS. 604.5 & 609.4.
 H CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS NOT SHOWN- SEC.
 AND FIGURE 604.7.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES NOT
 SHOWN- SEC. 606.2
 J) CAF? SINK HEIGHT, AND CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS NOT SHOWN- SEC. 606.2.
 K) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE SHOWERS
 NOT SHOWN- SEC. 608.2.2.1
 M) SHOWER GRAB BAR LENGTHS, AND MOUNTING HEIGHTS NOT
 SHOWN- SEC. 608.3.2.
 N) HEIGHT OF THE SHOWER CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SEC. 608.5.2.
  
 4) SHEETS P301, P302, P401, P402, P701: IT APPEARS THE
 PLUMBING FIXTURES IN THE BATHROOMS ARE BEING REPLACED.
 PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING
 MAKES AND MODELS AND ADA CONFORMANCE APPROVAL NOTED
 WHERE REQUIRED- SEC. 107.2.1 WPB.
  
 5) P302: NOTE 202 INDICATES THERE MAY BE A FOOD WASTE
 DISPOSER INSTALLED. PLEASE NOTE FOOD WASTE DISPOSERS
 SHALL NOT DISCHARGE INTO THE GREASE INTERCEPTOR-
 1003.3.2 FBC P.
  
 6) P701: A MEANS OF CONTROLLING THE HOT WATER DELIVERY
 TEMPERATURES AT THE NEW KITCHEN SINK AND DISHWASHER
 SHALL BE PROVIDED PER SEC. 607.1.1 FBC P. PLEASE NOTE
 THE MEANS OF CONTROL CANNOT BE THE THERMOSTAT ON THE
 EXISTING WATER HEATER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  