Plan Review Notes
Plan Review Notes For Permit 22080265
Permit Number 22080265
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-12 13:40:34FIRE PROVISO COMMENTS:
  
 (1) ANY MODIFICATIONS, ADDITIONS, CHANGES, ETC. TO ANY
 LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM)
 SHALL BE CONDUCTED UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 (2) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS OF DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS SHALL BE PROTECTED
 FROM DAMAGE DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (5) EXIT STAIRS SHALL NOT HAVE ANY OBSTRUCTIONS OR
 IMPEDIMENT TO EMERGENCY EGRESS, AND THE STAIRS SHALL
 NOT BE UTILIZED FOR MATERIAL STAGING.
  
 (6) THE SPACE BENEATH THE PERMANENT PLATFORMS SHALL NOT
 BE USED FOR STORAGE UNLESS IT HAS A ONE- HOUR FIRE
 RESISTANCE RATING.
  
 (7) ALL DOOR HARDWARE IN THE MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE.
  
 (8) ALL INTERIOR FINISHES AND FURNISHINGS SHALL COMPLY
 WITH NFPA 101, 10.2 AND 10.3
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  
  
  
  