| Plan Review Notes For Permit 22080265 |
| Permit Number |
22080265 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-03 09:27:36 | CHURCH 3RD AND 4TH FLOOR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THAT HAND RAILS ARE REQUIRED ON BOTH | | | SIDES OF THE PLATFORM STAIR - FBC 1011.11 HANDRAILS. | | | FLIGHTS OF STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE | | | AND SHALL COMPLY WITH SECTION 1014. | | | | | | 2) WHEN CALCULATING THE NUMBER OF OCCUPANTS FROM EACH | | | ROOM FROM DRAWING A2.1.1 (3RD FLOOR) - THE NUMBER OF | | | OCCUPANTS DO NOT MEET THE EXIT CAPACITY SHOWN FOR THE | | | DOOR OPENINGS. PLEASE RE EVALUATE YOUR OCCUPANCY | | | CALCULATIONS. DRAWING A0.1 AND A2.1.2 - SHOWS AN | | | OCCUPANT LOAD FOR WHICH FLOOR? AND IT DOES NOT INCLUDE | | | THE OFFICE AREA. FBC 1004.2.1 - - - FBC 1005.3 |
|