| 2022-11-21 08:32:54 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22080258 |
| | 11/21/22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2-01 GAS RISER: SHOW THE PIPE SIZE FROM THE |
| | REGULATOR TO GWH-1 AT THE LAUNDRY- TABLE 402.4(3). |
| | |
| | 2) P1-01B & P2-01: 2ND REQUEST TO PROVIDE COMBUSTION |
| | AIR AND VENTING PLANS FOR THE GAS WATER HEATERS- SECS. |
| | 304.1, 503.1 & 624.1.FBC FG. THE ARCHITECT???S RESPONSE |
| | INDICATES THE DETAILS ARE ON THE MECHANICAL PLANS |
| | HOWEVER THEY ARE NOT PROVIDED THERE. |
| | A) 2ND REQUEST TO PROVIDE MANUFACTURER???S |
| | SPECIFICATIONS FOR THE WATER HEATERS. |
| | B) PLEASE PROVIDE A FLOOR PLAN DRAWING SIMILAR TO SHEET |
| | P1-01B THAT SHOWS THE LOCATIONS OF THE 24- GAS WATER |
| | HEATERS AND GAS AND WATER PIPING LAYOUTS- SEC. 107.2.1 |
| | WPB. |
| | |
| | 3) P1-01B & P2-01: 2ND REQUEST TO PROVIDE COMBUSTION |
| | AIR AND VENTING PLANS FOR THE GAS DRYERS- SECS. 304.1, |
| | 614.1 & 614.4 FBC FG. THE ARCHITECT???S RESPONSE |
| | INDICATES THE DETAILS ARE ON THE MECHANICAL PLANS |
| | HOWEVER ONLY TWO 8-INCH VENTS ARE SHOWN ON M1-02B. |
| | THERE IS A NOTE ON THE PLAN REFERENCING THE SUBMITTED |
| | MANUFACTURER???S SPECIFICATIONS, HOWEVER THE COMBUSTION |
| | AIR AND VENTING INFORMATION (PAGE 37) IS NOT CONTAINED |
| | IN THE DOCUMENT. |
| | |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH, FL. 33401 |