| 2022-08-26 14:46:16 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22080258 |
| | 8/26/22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1-01B: PROVIDE A COMPLETE GAS RISER THAT |
| | INCLUDES THE NEW GAS PIPING TO THE WATER HEATER AND |
| | DRYERS, AND ALL EXISTING GAS PIPING AND APPLIANCES- |
| | SECS. 402.1 & 402.2 FBC FG. PLEASE INCLUDE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS INCLUDING |
| | THE PIPE SUPPLYING THE WATER HEATER. |
| | G) LOCATIONS OF REGULATORS AND SHUT OFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 2) P1-01B GAS WATER HEATER- FBC FG. |
| | A) PROVIDE AN EQUIPMENT SCHEDULE AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SEC. 624.1. |
| | B) PROVIDE COMBUSTION AIR AND VENTING PLANS- SECS. |
| | 304.1, 503.1 & 624.1. |
| | |
| | 3) P1-01B GAS DRYERS- FBC FG. |
| | A) PROVIDE AN EQUIPMENT SCHEDULE AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SEC. 613.1. |
| | B) PROVIDE COMBUSTION AIR AND EXHAUST PLANS- SECS. |
| | 304.1, 614.1 & 614.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |