| 2022-08-17 15:17:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF CO DETECTORS WITHIN THIS |
| | NEW HOTEL OCCUPANCY. |
| | |
| | PER NFPA 101 CH 28 |
| | |
| | 28.3.4.7 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE |
| | DETECTION SYSTEMS. |
| | |
| | 28.3.4.7.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE |
| | DETECTORS IN |
| | ACCORDANCE WITH SECTION 9.12 AND 28.3.4.7 SHALL BE |
| | PROVIDED IN NEW |
| | HOTELS AND DORMITORIES WHERE EITHER OF THE FOLLOWING |
| | CONDITIONS EXISTS: |
| | (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING |
| | ATTACHED GARAGES, |
| | UNLESS OTHERWISE EXEMPTED BY 28.3.4.7.3 |
| | (2) GUEST ROOMS OR GUEST SUITES CONTAINING A |
| | PERMANENTLY INSTALLED |
| | FUEL-BURNING APPLIANCE OR FUEL-BURNING FIREPLACE |
| | |
| | 28.3.4.7.2 WHERE REQUIRED BY 28.3.4.7, CARBON MONOXIDE |
| | ALARMS OR |
| | CARBON MONOXIDE DETECTORS SHALL BE INSTALLED IN THE |
| | FOLLOWING |
| | LOCATIONS: |
| | (1) OUTSIDE OF EACH SEPARATE GUEST ROOM OR GUEST SUITE |
| | SLEEPING AREA |
| | IN THE IMMEDIATE VICINITY OF THE SLEEPING ROOMS |
| | (2) ON EVERY OCCUPIABLE LEVEL OF A GUEST ROOM AND GUEST |
| | SUITE |
| | |
| | |
| | 28.3.4.7.3 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE |
| | DETECTORS AS |
| | SPECIFIED IN 28.3.4.7.1(1) SHALL NOT BE REQUIRED IN THE |
| | FOLLOWING |
| | LOCATIONS: |
| | (1) IN GARAGES |
| | (2) WITHIN GUEST ROOMS OR GUEST SUITES WITH |
| | COMMUNICATING ATTACHED |
| | GARAGES THAT ARE OPEN PARKING STRUCTURES AS DEFINED BY |
| | THE BUILDING |
| | CODE |
| | (3) WITHIN GUEST ROOMS OR GUEST SUITES WITH |
| | COMMUNICATING ATTACHED |
| | GARAGES THAT ARE MECHANICALLY VENTILATED IN ACCORDANCE |
| | WITH THE |
| | MECHANICAL CODE |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS AND |
| | SPECIFIC REFERNCES OF OMISSION. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER COMPIANCE |
| | AND OR EVALUATION FROM APARTMENT BUILDING VS HOTEL. |
| | |
| | PER NFPA 101 CH 28 |
| | |
| | 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 28.3.5.3. |
| | |
| | 28.3.5.3 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | IN ACCORDANCE WITH |
| | SECTION 9.7, AS MODIFIED BY 28.3.5.4. IN HOTEL OR |
| | DORMITORY OCCUPANCIES |
| | UP TO AND INCLUDING FOUR STORIES IN HEIGHT THAT ARE |
| | LOCATED-IN BUILDINGS |
| | NOT EXCEEDING 60 FT (18.3 M) IN HEIGHT ABOVE GRADE |
| | PLANE, SYSTEMS IN |
| | ACCORDANCE WITH NFPA 13R SHALL BE PERMITTED |
| | |
| | 28.3.5.6 LISTED QUICK-RESPONSE OR LISTED RESIDENTIAL |
| | SPRINKLERS SHALL BE |
| | USED THROUGHOUT GUEST ROOMS AND GUEST ROOM SUITES |
| | |
| | PLEASE PROVIDE A REVIEW OF COMPLIANCE FROM A QUALIFIED |
| | FIRE SPRINKLER CONTRACTOR WITH A NOTE OF ACKNOWLEGMENT |
| | TO COMPLY WITH SHOP DRAWINGS PROVIDED UNDER SEPARATE |
| | PERMIT. |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF EMERGENCY INSTRUCTIONS |
| | |
| | PER NFPA 101 CH 28 |
| | |
| | 28.7.4 EMERGENCY INSTRUCTIONS FOR RESIDENTS OR GUESTS. |
| | 28.7.4.1* A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR |
| | ARRANGEMENT, EXIT |
| | LOCATIONS, AND ROOM IDENTIFICATION SHALL BE POSTED IN A |
| | LOCATION AND |
| | MANNER ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION |
| | ON, OR IMMEDI ATELY ADJACENT TO, EVERY GUEST ROOM DOOR |
| | IN HOTELS AND IN EVERY RESIDENT |
| | ROOM IN DORMITORIES |
| | |
| | PLEASE REVIEW AND PROVIDE A DRAFT FOR REVIEW AND THE |
| | PROPOSED LOCATIONS(S) |
| | |
| | |
| | |
| | 4) THERE IS NO DOOR SCHEDULE INDICATING THE UNITS |
| | LOCKING AND LATCHING PER NFPA 101 CH 7 |
| | |
| | 28.2.2.2 DOORS. |
| | 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | PLEASE PROVIDE FOR ANY CHANGES TO THE DOOR HARDWARE |
| | LOCKING AND LATCHING AND OR PROVIDE A NOTE OF NO |
| | CHANGES. |
| | |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS OF ANY CHANGES TO THE |
| | ACCESS CONTROL OF THIS HOTEL OCCUPANCY. |
| | |
| | 28.2.2.2.2.2 DELAYED-EGRESS ELECTRICAL LOCKING SYSTEMS |
| | COMPLYING WITH |
| | 7.2.1.6.1 SHALL BE PERMITTED. |
| | 28.2.2.2.2.3 SENSOR-RELEASE OF ELECTRICAL LOCKING |
| | SYSTEMS COMPLYING |
| | WITH 7.2.1.6.2 SHALL BE PERMITTED |
| | |
| | ANY CHANGES TO THE ACCESS CONTROL SHALL BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEGMENT IF APPLICABLE. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |