| 2022-10-18 15:58:03 | 10/18/22 DISCUSSED WITH ROBERT BROWN THE ARMOR SCREEN |
| | TEST REPORT SENT BY BRYAN WASSON DIRECTOR OF DEALER |
| | RELATIONS OF ARMOR SCREEN CORPORATION. |
| | ROBERT BROWN WOULD ACCEPT THE TEST REPORT AS PART OF |
| | THE SITE SPECIFIC ENGINEERING PACKAGE FOR OPENING #2 IF |
| | THOMAS J. TWOMEY P.E. (ENGINEER OF RECORD) SUBMITS THE |
| | TEST REPORT AS APPROVED SHOP DRAWINGS. ENGINEER NEEDS |
| | TO REVIEW AND APPROVE IN WRITING THE TEST REPORT. |
| | NOTE: IN ADDITION NEEDS TO ADDRESS ALL OTHER BUILDING |
| | REVIEW COMMENTS AND ELECTRICAL COMMENTS. SEE PREVIOUS |
| | BUILDING REVIEW COMMENTS BELOW. |
| | |
| | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22080253 |
| | 8403 IRONHORSE CT. |
| | |
| | 1- ARMOR SCREEN ROLL-UP SHUTTERS: |
| | A) SHUTTERS INSTALLATION SCHEDULE SPECIFY CONCRETE AS |
| | THE SUBSTRATE WHERE SHUTTERS ARE GOING TO BE INSTALLED. |
| | ACCORDING TO CITY RECORDS, THE COLUMNS SUPPORTING THE |
| | ROLL-UP SHUTTERS ARE NOT CONCRETE. THEY ARE FILLED |
| | CONCRETE BLOCK COLUMNS. REVISE SHUTTERS INSTALLATION |
| | SCHEDULE TO REFLECT CORRECT SUBSTRATE. SEC. 107.2.1 |
| | CITY AMENDMENTS. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | B) ACCORDING TO LIMITATIONS OF USE ON SHEET 1 OF 12 OF |
| | INSTALLATION INSTRUCTIONS FOR FLORIDA PRODUCT APPROVAL |
| | FL320-R10, THE MAXIMUM SPAN IS 192 INCHES. THE SPAN FOR |
| | OPENING #2 EXCEEDS THE MAXIMUM SPAN ALLOWED BY THE |
| | PRODUCT APPROVAL. SITE SPECIFIC ENGINEERING SUBMITTED |
| | FROM THOMAS J. TWOMEY P.E. CAN NOT BE USED IS IT |
| | EXCEEDS THE LIMITATIONS OF THE PRODUCT APPROVAL. |
| | SHUTTERS NEED TO BE TESTED AS REQUIRED BY SEC. |
| | R301.2.1.2 FBC-RESIDENTIAL. |
| | |
| | 2- ACCORDING SHUTTERS: |
| | A) SHUTTERS INSTALLATION SCHEDULE SPECIFY CONCRETE AS |
| | THE SUBSTRATE WHERE SHUTTERS ARE GOING TO BE INSTALLED |
| | (TOP AND BOTTOM). TYPICALLY THE BOTTOM OF WINDOW |
| | OPENINGS IS CONCRETE BLOCK. REVISE INSTALLATION |
| | SCHEDULE USING THE ANCHOR FOR CONCRETE BLOCK SUBSTRATE |
| | AT THE BOTTOM OR PROVIDE PROOF SHOWING BOTTOM OF |
| | OPENINGS HAS POURED CONCRETE WITH THE STRENGTH |
| | SPECIFIED ON ANCHOR SCHEDULE OF PRODUCT APPROVAL |
| | SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B) REVISE SHUTTER GLASS SEPARATION SPECIFIED ON SHUTTER |
| | INSTALLATION SCHEDULE FOR OPENINGS WITH A SHUTTER SPAN |
| | LONGER THAN 99 INCHES. SEE SHEET 13 OF 13 OF SHUTTERS |
| | PRODUCT APPROVAL AND REVISE AS REQUIRED. NEED 3-1/2 |
| | INCH GLASS SEPARATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |